Rockwell Automation Publication 1756-RM012B-EN-P - April 2018
9
Chapter
1
Safety Integrity Level (SIL) Concept
SIL Certification
This section provides the SIL certifications and Performance Level for the
controllers.
TÜV Rheinland has approved GuardLogix 5580 and Compact GuardLogix
5380 controller systems for use in safety-related applications where the de-
energized state is considered to be the safe state.
All I/O examples in this manual are based on achieving de-energization as the
safe state for typical machine safety and Emergency Shutdown (ESD) systems.
Topic
Page
Contact Information If Device Failure Occurs
Controller System
IEC 61508
IEC 62061
ISO 13849-1
Type-approved and
certified for use in
safety applications up
to and including:
Suitable for use in
safety applications up
to and including:
Suitable for use in safety
applications up to and including:
GuardLogix 5580
controller systems
SIL 2
(2)
SIL 3
(3)
(2) Primary controller that is used without a safety partner.
(3) Primary controller that is used with a safety partner.
SIL CL2
SIL CL3
Performance Level PLd (Cat. 3)
Performance Level PLe (Cat. 4)
Compact GuardLogix 5380
SIL 2 controller systems
(1)
(1) Compact GuardLogix 5380 controller catalog numbers with a ‘2’ at the end, for example, 5069-L3
xxxxx
S2, are for use in safety
applications up to and including SIL 2.
SIL 2
SIL CL2
Performance Level PLd (Cat. 3)
IMPORTANT
In the remainder of this publication:
• SIL 2 represents SIL 2, SIL CL2, and PLd
• SIL 3 represents SIL 3, SIL CL3, and PLe
Содержание Compact GuardLogix 5380
Страница 62: ...62 Rockwell Automation Publication 1756 RM012B EN P April 2018 Chapter 6 Safety Application Development Notes...
Страница 88: ...88 Rockwell Automation Publication 1756 RM012B EN P April 2018 Appendix C Reaction Times Notes...
Страница 108: ...108 Rockwell Automation Publication 1756 RM012B EN P April 2018 Glossary Notes...
Страница 114: ...114 Rockwell Automation Publication 1756 RM012B EN P April 2018 Index...
Страница 115: ......