72
Rockwell Automation Publication 1756-RM012B-EN-P - April 2018
Appendix A
Safety Instructions
See the following publications for more information.
Table 9 - Drive Safety Instructions
(1)
Mnemonic
Name
Purpose
SS1
Safe Stop 1
The Safe Stop 1 instruction monitors the deceleration of an axis according to the specified velocity ramp to zero speed and controls
its output (O1) to initiate Safe Torque Off (STO).
SS2
Safe Stop 2
The Safe Stop 2 instruction initiates and monitors the motor deceleration within set limits to verify that the motor is brought to an
operational stop. Once stopped, SS2 continues to monitor the operational stop of the motor.
SOS
Safe Operating Stop
The Safe Operating Stop instruction monitors the speed or position of a motor or axis to verify that the deviation from standstill
speed or position is not more than a defined amount.
SLS
Safely-limited Speed
The Safely-limited Speed instruction monitors the speed of an axis and sets the SLS Limit output if the speed exceeds the Active
Limit input value for the instruction.
SLP
Safe Limited Position
The Safely-limited Position instruction monitors the position of a motor or axis to verify that the position does not deviate above or
below defined limits.
SDI
Safe Direction
The Safe Direction instruction monitors position of a motor or axis to detect movement of more than a defined amount in the
unintended direction.
SBC
Safe Brake Control
The Safe Brake Control (SBC) instruction:
• Controls safety outputs that actuate a brake.
• Sets timing between brake and Torque Off Request outputs.
• Monitors brake feedback and I/O status.
SFX
Safe Feedback Scaling
The Safety Feedback Interface instruction converts motor velocity and position feedback from a drive module into user scaling units.
It also defines an absolute reference position.
(1) Motion safety instructions are available when using a GuardLogix 5580 controller, Compact GuardLogix 5380, and Kinetix 5700 ERS4 drives with the Studio 5000 Logix Designer application (V31
or later).
IMPORTANT
If you use Motion Direct Commands with a Kinetix 5500 drive, Kinetix 5700
servo drive, or a PowerFlex 527 drive, see the user manual for the drive for
information on how to use this feature in safety applications.
• Kinetix 5500 Servo Drives User Manual, publication
• Kinetix 5700 Servo Drives User Manual, publication
• PowerFlex 527 Adjustable Frequency AC Drive User Manual,
publication
Table 10 - Additional Resources
Resource
Description
GuardLogix Safety Application Instruction Set
Reference Manual, publication
Provides more information on the safety application
instructions.
Logix5000 Controllers Generals Instructions
Reference Manual, publication
Provides information on the Logix5000 instruction set that
includes general, motion, and process instructions.
Содержание Compact GuardLogix 5380
Страница 62: ...62 Rockwell Automation Publication 1756 RM012B EN P April 2018 Chapter 6 Safety Application Development Notes...
Страница 88: ...88 Rockwell Automation Publication 1756 RM012B EN P April 2018 Appendix C Reaction Times Notes...
Страница 108: ...108 Rockwell Automation Publication 1756 RM012B EN P April 2018 Glossary Notes...
Страница 114: ...114 Rockwell Automation Publication 1756 RM012B EN P April 2018 Index...
Страница 115: ......