60
Rockwell Automation Publication 1756-RM012B-EN-P - April 2018
Chapter 6
Safety Application Development
Performing Online Edits
If online edits affect the safety program, you must revalidate all affected
elements of the application, as determined by the impact analysis, before you
resume operation.
shows the process for online editing.
The safety-lock and safety signature features of the GuardLogix controller
affect online edits.
See
Generate the Safety Signature on page 52
for more information.
For detailed information on how to edit Ladder Logic in the Studio 5000
Logix Designer application while online, see the Logix5000 Controllers Quick
Start, publication
.
Modification Impact Test
Any modification, enhancement, or adaptation of your validated software must
be planned and analyzed for any impact to the functional safety system. All
appropriate phases of the software safety lifecycle must be conducted as
indicated by the impact analysis.
At a minimum, you must perform these actions:
• Functional tests of all impacted software.
• Document all modifications to your software specifications.
• Document all test results.
For detailed information, see IEC 61508-3, Section 7.8 Software
Modification.
TIP
Limit online edits to minor program modifications such as setpoint changes or
minor logic additions, deletions, and modifications.
Содержание Compact GuardLogix 5380
Страница 62: ...62 Rockwell Automation Publication 1756 RM012B EN P April 2018 Chapter 6 Safety Application Development Notes...
Страница 88: ...88 Rockwell Automation Publication 1756 RM012B EN P April 2018 Appendix C Reaction Times Notes...
Страница 108: ...108 Rockwell Automation Publication 1756 RM012B EN P April 2018 Glossary Notes...
Страница 114: ...114 Rockwell Automation Publication 1756 RM012B EN P April 2018 Index...
Страница 115: ......