Rockwell Automation Publication 2100-IN012G-EN-P - August 2016
63
Installing and Removing Plug-in Units
Chapter 4
For CENTERLINE MCC units with the 100 ms arc duration rating,
there is an additional screw that secures the unit support pan. This screw
is at the left-rear corner of the unit support pan.
3. Lift the right side of the support pan approximately 4 in. (102 mm).
4. Pull the right side of the support pan forward to release from the left
rear slot on the structure.
5. Push back on the left side of the support pan until the support pan is free
from the structure.
Vertical sections can be supplied with plug-in stab opening protective
caps, manual shutters, or automatic shutters. Refer to the next step if any
of these options are supplied.
6. Carefully install the protective caps or close the manual shutters after the
unit is removed.
Automatic shutters close as the units are removed.
ATTENTION:
All covers and doors must be in place before applying power to
the MCC. If units are removed, they must be replaced with the appropriate
items such as units, doors, and unit support pans.
Unit Support Pan
Unit Support
Pan Screw
Содержание CENTERLINE 2100