Rockwell Automation Publication 2100-IN012G-EN-P - August 2016
61
Installing and Removing Plug-in Units
Chapter 4
9. Remove the unit from the MCC.
10. Carefully install protective caps or close the manual shutters after unit is
removed.
Automatic shutters close as units are removed.
11. See the next section for additional information.
ATTENTION:
All covers and doors must be in place before applying power to
the MCC. If units are removed, they must be replaced with the appropriate
items such as units, doors, and unit support pans.
ATTENTION:
All covers and doors must be in place before applying power to
the MCC. If units are removed, they must be replaced with the appropriate
items such as units, doors, and unit support pans.
When installing units for CENTERLINE 2100 Motor Control Centers with the
ArcShield rating, you must make sure you are installing a unit that has the same
arc resistance rating as the MCC in which it is being installed. The arc resistance
rating can be found on the ArcShield label on the vertical wireway door.
Units that are not rated for 100 ms arc duration must not be installed in a
section that is rated for 100 ms arc duration. The arc resistant rating does not
apply if that is done.
Содержание CENTERLINE 2100
Страница 4: ...4 Rockwell Automation Publication 2100 IN012G EN P August 2016 Summary of Changes Notes ...
Страница 106: ...106 Rockwell Automation Publication 2100 IN012G EN P August 2016 Chapter 10 Maintenance after Fault Condition Notes ...
Страница 108: ...108 Rockwell Automation Publication 2100 IN012G EN P August 2016 Chapter 11 Renewal Parts Notes ...
Страница 134: ...134 Rockwell Automation Publication 2100 IN012G EN P August 2016 Index Notes ...
Страница 135: ......