192
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter A
Specifications
DeviceNet
Communication Card
Electrical (DeviceNet)
Supply Voltage
11…25 V DC
Input Current
0.085 A max. / 0.035 A typical
Power Consumption
2.04 W max. / 0.84 W typical
Environmental
Ambient Temperature
Operating
Storage
-20…+60°C
-40…+85°C (-40…185°F)
Humidity (operating)
5…95% non-condensing
Vibration (per IEC 68-2-6)
5G
Shock (per IEC 68-2-27)
30G
Communication
Baud Rates
125, 250, 500 kbps
Distance (max)
@ 125 kbps
@ 250 kbps
@ 500 kbps
500 m (1640 ft)
200 m (656 ft)
100 m (328 ft)
Standards
CSA 22.2 No. 14, EN 60947-4-1, EN 60947-5-1, UL 508
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......