148
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 11
Testing & Troubleshooting
•
PC with Serial Port, MPS Explorer software, and serial communication
cable
•
Terminal Emulation Software
•
Serial Communication Cable
•
AC and DC Elementary Schematics
•
Wiring Diagrams (for this relay installation)
•
Continuity Tester
•
Protective Relay AC Test Source
–
Minimum: single-phase voltage and current with phase angle control
–
Preferred: three-phase voltage and current with phase angle control
Procedure
1.
Remove the control voltage and AC signals from the 825-P by opening the
appropriate breakers or removing fuses.
2.
Isolate the relay trip contact.
3.
Verify the correct AC and DC connections by performing point-to-point
continuity checks on the associated circuits.
4.
Apply AC or DC control voltage to the relay.
5.
After the relay is energized, the front panel green
ENABLE
LED
illuminates.
6.
Connect a PC to the relay using an appropriate serial cable.
7.
Start the MPS Explorer software and establish communication with the
relay.
8.
Set the correct relay time and date using either the front panel or MPS
Explorer software.
9.
Enter the relay settings for your application.
10.
If you are connecting an external RTD scanner, follow the substeps below;
otherwise continue with Step 11.
a. Connect the fiber optic cable to the module fiber optic output.
b. Plug the relay end of the fiber optic cable into the relay fiber optic input.
11.
Verify the relay AC connections.
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......