
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
107
Metering & Monitoring
Chapter
7
The thermal meter function also reports the state of connected RTDs if any have
failed. Table 48 shows failure messages.
Power Measurement
Conventions
The 825-P uses the IEEE convention for power measurement assuming motor
action. The implications of this convention are shown in Figure 35.
Figure 35 - Complex Power Measurement Conventions
In the 825-P, reported positive real power is always into the motor.
Table 48 - RTD Input Status Messages
Message
Status
Open
RTD leads open
Short
RTD leads shorted
Comm Fail
Fiber-optic communications to 825-PR12D Module have failed
Stat Fail
825-PR12D Module self-test status failure
Power Into Motor
Q+ (VAR)
I leads V
W = –
VAR = –
PF = LAG
I lags V
W = –
VAR = +
PF = LEAD
P+ (W)
I leads V
W = +
VAR = –
PF = LEAD
I lags V
W = +
VAR = +
PF = LAG
M
825-P
Relay
Source
Bus
Direction of
Positive Real Power
Motor
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......