Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module
5-7
Table 5.7 1794-IE8H Interpretation of Calibration Data Structure Content During Read Access (Pending Status)
Command Byte
Item Byte
Data1
Byte
Data2
Byte
Status (Binary)
Command Bits 0…5 (Decimal)
10
Pending
1
Calibration of offset at 25 °C is in process
according to channel-mask
Channel-Mask
0
0
2
Calibration of gain at 25 °C is in process according
to channel-mask
3…7
The unknown command is trying to be interpreted
x
(2)
x
(2)
x
(2)
8
All calibration values are set to default
0
0
0
9
The specified calibration value is set to default
Value-identifier
10
Reserved
(1)
Reserved
(1)
Reserved
(1)
Reserved
(1)
11
Reserved
(1)
12
Reserved
(1)
13
Reserved
(1)
14
The calibration content is saved to EEPROM
x
(2)
x
(2)
x
(2)
15…61 Unknown command is mirrored back
0
0
0
62
Reserved
Reserved
Reserved
Reserved
63
Reserved
(1)
Reserved. Used during manufacture of the product. Do not use.
(2)
The received values are mirrored back.
Содержание 1794-IE8H
Страница 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Страница 6: ......
Страница 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Страница 46: ...Publication 1794 UM063A EN P March 2006 2 22 Configurable FLEX I O Analog Module Features Notes...
Страница 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Страница 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Страница 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Страница 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Страница 145: ......