Publication 1794-UM063A-EN-P - March 2006
2-20
Configurable FLEX I/O Analog Module Features
Secondary Master Enable (SME) and Primary Master Inhibit (PMI)
These two bits control a few module internal functions individually for
channels 0 to 7.
HART Status Indicators
When this bit is set, the indicators are used for HART diagnostics. indicator
behavior changes to show communication on HART with each indicator
representing a HART loop. A flashing yellow indicator means that
communication is currently being processed while a solid yellow indicator
means that this device is in the transmitter list.
HART Status Inhibit
When this bit is set, the HART communication status is not shown in the
realtime data table to enable compatibility. The appropriate areas are cleared
with zeroes.
50 or 60 Hz Filter
The values are:
•
0 = 50 Hz (default)
•
1 = 60 Hz
Table 2.18 SME and PMI Values
Bits
(1)
1 (Default)
2
3
4
PMI
8, 9, 10, 11, 12,
13, 14, 15
0
0
1
1
SME
0, 1, 2, 3, 4, 5, 6, 7
0
1
0
1
HART Smooth Filter
Pulsed
On
Off
On
Rebuild
On
On
Off
Off
HART Read Back
On
On
Off
Off
Primary Master
On
On
Off
Off
Secondary Master
Off
On
Off
On
1
Where:
Ch0 - bits 0 and 8; Ch1 - bits 1 and 9; Ch2 - bits 2 and 10; Ch3 - bits 3 and 11;
Ch4 - bits 4 and 12; Ch5 - bits 5 and 13; Ch6 - bits 6 and 14; Ch7 - bits 7 and 15
Содержание 1794-IE8H
Страница 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Страница 6: ......
Страница 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Страница 46: ...Publication 1794 UM063A EN P March 2006 2 22 Configurable FLEX I O Analog Module Features Notes...
Страница 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Страница 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Страница 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Страница 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Страница 145: ......