Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module
5-3
1794-IE8H Calibration
Command Structure
Calibration of the HART I/O module is performed using data structures and
MSG Ladder-logic instructions. The MSG instruction sends the data structure
to a dedicated attribute in the FLEX HART I/O module and the associated
response is read from the same attribute. The data structure contains
commands and its associated parameters. Depending on the command, they
are either writable or readable. Only one access, either read or write, is
executable at a time.
The Calibration data structure has four members: Command, Item, Data1, and
Data2.
Table 5.2 Calibration Data Structure
Attribute
Field Size
Implementation
Description
Value (Hex)
Access
67
hex
4 byte
struct {
Conditional
Read or write
USINT Command;
Calibration command;
USINT Item;
Additional command
information;
USINT Data1;
Data according to command;
USINT Data2;
Data according to command
} Calibration;
Содержание 1794-IE8H
Страница 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Страница 6: ......
Страница 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Страница 46: ...Publication 1794 UM063A EN P March 2006 2 22 Configurable FLEX I O Analog Module Features Notes...
Страница 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Страница 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Страница 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Страница 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Страница 145: ......