Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
29
Install the 1756-L7x Controller
Chapter 1
.
Uninstall the ESM
Consider these points before removing the ESM:
•
The following ESM modules can be currently installed in your 1756-L7
x
or 1756-L7
x
XT controller:
–
1756-ESMCAP
–
1756-ESMNSE
–
1756-ESMCAPXT
–
1756-ESMNSEXT
IMPORTANT
Allow the ESM to finish charging before removing power from the controller.
Failure to do so can result in the loss of the application program. A type 1,
code 40 major fault is logged on powerup.
To verify that the ESM is fully charged, check the status display to confirm that
messages CHRG or ESM charging are no longer indicated.
TIP
We recommend that you check the WallClockTime object attributes after
installing an ESM to verify that time of the controller is correct.
The ESM contains a real-time clock. If the ESM is new or came from another
controller, the WallClockTime object attributes for your controller can change.
WARNING:
If your application requires the ESM to deplete its residual stored
energy to 40 μJoule or less before you transport it into or out of the application,
use only the
1756-(SP)ESMNSE(XT)
module. In this case, complete these steps
before you remove the ESM.
•
Turn power off to the chassis.
After you turn power off to the chassis, the controller’s OK status indicator
transitions from green to solid red to OFF.
•
Wait
at least 20 minutes
for the residual stored energy to decrease to
40 μJoule or less before you remove the ESM.
There is no visual indication of when the 20 minutes has expired.
You must track
that time period
.
WARNING:
When you insert or remove the energy storage module while
backplane power is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector.
IMPORTANT
Before you remove an ESM, make necessary adjustments to your program
to account for potential changes to the WallClockTime attribute.
Содержание 1756-L63XT
Страница 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Страница 78: ...78 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 3 Start Using the Controller Notes...
Страница 126: ...126 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 7 Manage Controller Communication Notes...
Страница 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Страница 168: ...168 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 10 Develop Applications Notes...
Страница 182: ...182 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 12 Redundant Systems Notes...
Страница 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Страница 211: ......