Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
175
Chapter
12
Redundant Systems
ControlLogix Redundancy
Overview
Redundancy provides more system availability by switching control to a
secondary controller chassis if a fault occurs in the primary controller chassis.
The redundant system switches control from the primary to the secondary when
these faults occur:
•
Power loss to primary chassis
•
Hardware or firmware failure of any module in the primary chassis
•
A major fault in the user program on the primary controller
•
Loss of communication between the primary chassis and remote
ControlNet or EtherNet/IP modules
•
Disconnection of an Ethernet patch cable from an EtherNet/IP
communication module in the primary chassis
•
Removal or insertion of any module in the primary chassis
•
A user command that causes a switchover
Topic
Page
ControlLogix Redundancy Overview
ControlNet Considerations in Redundant Systems
Содержание 1756-L63XT
Страница 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Страница 78: ...78 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 3 Start Using the Controller Notes...
Страница 126: ...126 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 7 Manage Controller Communication Notes...
Страница 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Страница 168: ...168 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 10 Develop Applications Notes...
Страница 182: ...182 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 12 Redundant Systems Notes...
Страница 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Страница 211: ......