    Configuring the Device 

 

External power supply 

  Connect an external power supply's functional grounding to PE on the PoE terminal board's 3-pin 

terminal strip. When using an external power supply, connect the functional grounding to PE on the 
PoE terminal board. 

See also 

Unplugging the RJ45 connector ............................................................................................. 14 

 

 

4.5  Service interface 

For service purposes, you require the service kit 75-99-0006. The kit includes a USB-to-serial adapter 
and a 14-pin ribbon cable with adapter. 

See the instructions included in the service kit for a detailed description. 

 

5  Configuring the Device 

Once the connection has been established, the device must be configured. Configuration requires 
extensive system knowledge and may be carried out only by authorized personnel. 

 

5.1  Configuring the device using "OC Task" 

The software for configuring the device and displaying device functions is called 

OC Task

 and is available 

on the device. OC Task contains a number of commands that are used for administrative purposes. 

To access OC task, the device must be connected to a computer. This can take place: 

 

with a TCP/IP network via TELNET or SSH connection. Use the factory-set IP address (see label on 
housing) or the IP address 172.18.70.52. 

 

via the RS-232 service interface and the Hyper-Terminal software. 

Access to the console and Linux commands is granted after logging in with 

root

 and entering the 

corresponding password. If you have any questions, please contact your system administrator or the 
technical support team of Interflex Datensysteme GmbH. 

The 

root@

 prompt signals readiness to receive commands and data. 

The following input syntax must be observed: 

 

Commands are written in lowercase letters. 

 

Options are separated from the command by a blank and the minus sign. 

 

An overview of the command options can be retrieved with 

-?

 

Press the "ENTER" key to confirm command lines and data. 

 

To save new data, you must confirm the prompt 

Write to EEPROM (y/n)? 

with 

y

 

Modified data only becomes effective after a "Restart", e.g. after a cold boot. 

 

TELNET and SSH connections must be properly terminated after configuration. 

 

5.2  Switching on the power supply 

After the power supply has been switched on, the device executes the following functions: 

 

The operating system is booted. 

 

The applications are started. 

 

The connected slave terminals are connected to each other. 

The start-up procedure lasts up to 30 seconds. When the RUN LED lights up, a TELNET connection is 
possible. 

 

Содержание Interflex IF-572x

Страница 1: ......

Страница 2: ......

Страница 3: ...manual which is subject to change without prior notice Interflex Datensysteme GmbH does not enter into any commitment Copyright 2017 Version Date July 26 2017 Interflex Datensysteme GmbH Allegion Zett...

Страница 4: ......

Страница 5: ...the Device 7 4 1 Risk of electric shock 7 4 2 Electrostatic discharge ESD 7 4 3 Reader electronics to PoE terminal board 8 4 4 Power supply 8 4 5 Service interface 9 5 Configuring the Device 9 5 1 Con...

Страница 6: ...ii Contents 7 Accessories Overview 15 8 Technical Specifications 15 8 1 EU Declaration of Conformity 16 8 2 Open source program packages 16 9 Disposal 16...

Страница 7: ...tions described in this document if you belong to this target group 1 3 Symbols used in this document Warnings warn against hazards that may arise when using the devices described in the document The...

Страница 8: ...is device in environments exposed to explosion hazards 1 6 All specifications are subject to change without notice All information contained in this documentation is accurate at the time of printing A...

Страница 9: ...handles functions of the time recording access control program writes offline NetworkOnCard data onto credentials Allows for connection of an I O controller board optional additional hardware required...

Страница 10: ...18 70 52 and temporarily store the specified IP address 8 Adhesive tape Is applied over the mortise lock to prevent electrostatic discharges 9 Reset button Ends active processes and triggers a reboot...

Страница 11: ...contacts control cable 100 m JY ST Y 2 x 2 x 0 6 mm RS 485 bus cable to parent or child devices 1 200 m JY ST Y 2 x 2 x 0 6 mm RS 485 branch cable to bus cable 100 m JY ST Y 2 x 2 x 0 6 mm Cable lengt...

Страница 12: ...a positive decision a booking response and or a signal for activating an output relay for example are transmitted to the booking location If the decision is negative the reason for the booking rejecti...

Страница 13: ...strain relief if necessary The device must be connected via an external separator to ensure that it can be disconnected from the mains power supply The device must be equipped with an external fuse pr...

Страница 14: ...using the supplied ribbon cable as shown 4 4 Power supply Power can be supplied via PoE device IEE 802 3 of power class 3 up to 13 W and RJ 45 cable 18 to 24 VAC VDC power supply unit The RJ45 cable...

Страница 15: ...onnection Use the factory set IP address see label on housing or the IP address 172 18 70 52 via the RS 232 service interface and the Hyper Terminal software Access to the console and Linux commands i...

Страница 16: ...no netpar s reboot system netpar y enable DHCP netpar y print this screen 5 4 1 Setting network parameters netpar x The command netpar x shows you the current network parameters e g the IP address and...

Страница 17: ...e allows 8 terminals as maximum Explanation for devices of the IF 1xxx series Term Description host baud rate 1 1 200 2 9 600 3 19 200 Token ring baud rate Baud rate TCP IP network 0 4 MB 1 16 MB Baud...

Страница 18: ...shbox I O I O controller boards of the slave terminals The characters mean 1st First I O controller board for door control is ready for operation 2nd Second I O controller board I O extension board is...

Страница 19: ...files are available File name Purpose setpathvars bat You require this file for all updates You can enter the system password here in order to make it invisible in cmd exe You can also change the pat...

Страница 20: ...if5735 00403755 2016 05 21 xml Meaning of the name The new file is of type if5735 The serial number is 00403755 The file was created on 2016 05 21 Performing upgrade Start cmd exe and run batch file F...

Страница 21: ...sion Interface expander Order Number Item 75 5735 0003 Interface expander for I O expansion 8 Technical Specifications Electrical Data Power Supply 18 to 24 VAC VDC PoE device IEE 802 3 of power class...

Страница 22: ...ysically performing source distribution Interflex offers to provide you with a medium customarily used for software interchange containing a complete machine readable copy of the source code of the pr...

Отзывы: