120V AC 60Hz 1000W
L
L
N N
INPUT
OUTPUT
RLY 1
COMMON
N.O.
RLY 2
COMMON
N.O.
Please follow these steps to connect inverter to Load/Grid:
1. Before making Load/Grid connection, be sure to open DC protector/breaker first.
2. Strip each individual wire/conductor about 3/8”.
3. Connect grid wires according to polarity indicated on terminal block and tighten the
terminal screws. Be sure to connect protective earth conductor
( )
first.
-> Ground (green)
L-> LINE (black)
N-> Neutral (white)
4. Then, connect Load (output) wires according to polarity indicated on terminal block and
tighten terminal screws. Be sure to connect protective earth conductor
( )
first.
-> Ground (green)
L-> LINE (black)
N-> Neutral (white)
120V AC 60Hz 1000W
L
L
N N
INPUT
OUTPUT
RLY 1
COMMON
N.O.
RLY 2
COMMON
N.O.
AC output
(load)
5. Make sure all wires are securely connected.
CAUTION:
Appliances such as air conditioner require at least 2~3 minutes to restart
to have enough time to balance refrigerant gas inside of circuits. If a power outage
occurs and recovers in a short time, it will cause damage to your connected appliance.
To prevent this kind of damage, please check manufacturer of air conditioner if it’s
equipped with time-delay function before installation. Otherwise, this inverter will
trigger overload fault and cut off output to protect your appliance but it is still possible
it will cause internal damage to the air conditioner.
Содержание APS1000-12
Страница 1: ...POWER INVERTER APS1000 12 APS2000 24...
Страница 6: ...Battery Type Selector Charge Current Adjuster 25 50 75 100...
Страница 13: ...120Vac 75Vac 2 80Vac 2 140Vac 140Vrms 135Vac 2 2 30A 40A APS1000 12 APS2000 24 Same as Input Waveform...
Страница 16: ......
Страница 20: ...By restarting the inverter Turn it OFF and back ON...
Страница 23: ......
Страница 24: ...420 00233 03 POWER INVERTER...