6 Setup diagram
6.2
ThinkTop
®
setup utilising local ’I’ and ’II’ keys
General
Default is:
Step 2, tolerance is +/- 5 mm
Step 3-8, disabled
Timeout:
A 60 sec. timeout is started as soon as any button(s) is released.
On timeout the setup is exited with no changes saved.
Flashing LED means no value set. Steady LED means value set as shown
[D] LED:
Active during set-up:
Flashing in step 1
Steady in all other steps
Or during operations, error condition: Steady showing hardware fault, indication pin out of range
Flashing showing software fault
General commands in each step (except step 1):
5s
Next step / skip step
(In step 3-6 the program automatically moves to the next step
when a position is stored)
5s
Clear / disable step
(In step 2 this resets the unit to default)
(The command is accepted when all unlit LED’s flash briefly)
IIt is recommended to reset the unit before performing a setup.
Symbols
5s
Push local key “I”
5s
Push local key “II”
5s
Hold key “II” for 5 sec
Simple representation of LED indication:
Yellow
B
IR-Reciver
Red
D
Steady LED
Yellow
C
Green
E
Orange
F
Yellow
A
Flashing LED
22