6 Setup diagram
6.3
ThinkTop
®
Quick setup guide
Valve: Unique SSV, SRC/ARC type NC (selfadjustment disabled)
Push:
I
- and wait until red LED flashes
Push:
I
Push:
II
- hold for 5 sec (clear all stored parameters)
Push:
II
(red + yellow LED)
Push:
II
(red + green LED)
Push:
II
(red + green + orange LED)
Push:
II
(red + green + yellow LED)
Push:
I
Push:
II
- to approve valve down (closed)
Activate
Valve opens
Push:
II
- to approve (open)
Push:
I
(no upper seat-lift)
Push:
I
(no lower seat-lift)
Push:
I
(no self adjustment)
Push:
I
(no maintenance)
Push:
II
Red LED flashes (save & exit by push)
Setup done
Valve: SRC/ARC type NO (selfadjustment enabled)
Push:
I
- and wait until red LED flashes
Push:
I
Push:
II
- hold for 5 sec (clear all stored parameters)
Push:
II
(red + yellow LED)
Push:
I
Activate
Valve closes
Push:
II
- to approve valve closed
Push:
Deactivate
Valve opens
Push:
II
- to approve valve is open
Push:
I
(no upper seat-lift)
Push:
I
(no lower seat-lift)
Push:
II
= self adjustment
Push:
I
Push:
I
(no maintenance)
Push:
II
Red LED flashes (save & exit by push)
Setup done
Valve: LKB Valve (Butterfly) NC
Push:
I
- and wait until red LED flashes
Push:
I
Push:
II
- hold for 5 sec
Push:
II
(red + yellow LED)
Push:
II
(red + green LED)
I
Push:
II
- to approve valve closed (indication stem up)
Push:
Activate
LKB valve- open position (indication-stem down)
Push:
II
- to approve valve is open
Push:
I
(no upper seat-lift)
Push:
I
(no lower seat-lift)
Push:
I
(no self adjustment)
Push:
I
(no maintenance)
Push:
II
Red LED flashes (save & exit by push)
Setup done
24