4 Technical specifications
Micro environment demand specifications
Temperature
Working:
-20°C to +85°C
IEC 68-2-1/2
Storage:
-40°C to +85°C
IEC 68-2-1/2
Temperature change:
-25°C to +70°C
IEC 68-2-14
Vibration
10-55 Hz, 0.7 mm
IEC 68-2-6
55-500 Hz, 10g
3 x 30 min, 1 octave/min
Drop test
IEC 68-2-32
Humidity
Constant humidity:
+40°C, 21 days, 93% R.H.
IEC 68-2-3
Cyclic humidity:
+25°C/+55°C
12 cycles
IEC 68-2-30
(working)
93% R.H.
Protection class
IP66 and IP67
IEC 529
Input treshold
Voltage/current:
Type 1 input requirements
EN 61131-2
EMC Directive
2004/108/EF
EN 61000-6-3, EN 61000-6-2
AS-Interface
Version 2.1*)
EN50295
Version 3.0 **)
UL Approval
8-30 VAC/VDC, Class 2 input,
45 mA max. output
UL 508-E203255
*) Max. 31 ThinkTop units on a single master/gateway. **) Max. 62 ThinkTop units on a single master/gateway.