![ALENCON SPOT-V7 Series Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/alencon/spot-v7-series/spot-v7-series_manual_2893961031.webp)
Alencon SPOT: Installation,
Operation, and Maintenance Manual
30 |
P a g e
8.4.3 Mounting Procedure – Vertical Rail Mount
The SPOT can be easily mounted using standard Unistrut© along with spring loaded channel
nuts. The SPOT V7 comes with a hooked backplate that allows for the SPOT to be hung on the
Unistrut and then fastened using a Hex head screw. Recommended hardware for mounting is
as follows:
Unistrut© – Any typical zinc plated or galvanized steel Unistrut
Strut Channel Nuts with Spring, 13/16" Channel High, 5/16-18 Thread – x2 per SPOT
Hex Head Screw, Grade 8 Steel, 5/16"-18 Thread Size, 1" Long – x2 per SPOT
Based on OSHA and safety best practices documented in
the U.S., as well as others stated in Canada, Europe and
Asia, the SPOT should be lifted into position by two
people as it weighs approximately 51.25 kg (113 lbs.).
To properly hang the SPOT onto a Unistrut:
1)
Ensure you have a strong base to mount the SPOT as seen in the image below.
2)
The SPOT should be lifted into position by two people as it weighs approximately 51 - 69
kg. Ensure that the SPOT is resting on the floor securely. The side with the mounting
plate/bracket should be facing the floor.
3)
Ensure H4 connectors, cooling fans and RJ-45 connector ports are free from stress.
Do not hold by any of these points when lifting.
4)
Strategically place your hands and once ready lift the SPOT
5)
Lift the SPOT until the hooked mounting plate (highlighted in orange) lines up with the
Unistrut.
6)
Once everything is lined up you are ready to hook the SPOT in place as seen below
7)
Once SPOT is secured in place you must fasten the other end of the mounting bracket it
to the Unistrut using 5/16
th
Hex Head Screws