![ALENCON SPOT-V7 Series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/alencon/spot-v7-series/spot-v7-series_manual_2893961030.webp)
Alencon SPOT: Installation,
Operation, and Maintenance Manual
29 |
P a g e
Clearance:
For optimal and safe operation, make sure that the SPOT has enough clearance
around the unit. If the recommended minimum clearances in table below are not met, rated
performance may not be achieved.
Direction
Recommended Clearance
Above
12 inches
Below
24 inches
In front
12 inches, more recommended to allow the access
to the unit
On sides
12 inches, more recommended in hot climates to
prevent thermal de-rating
8.4.2 Selecting Location – Horizontal Rack Mount
The following considerations should be made when selecting the mounting location for the
SPOT power optimizer with FEED add-on:
Indoor/Outdoor:
The SPOT with FEED must be mounted indoors as the FEED enclosure is not
outdoor rated.
Mounting Position:
The SPOT can be mounted horizontally into a rack, 19” rack-mount
configuration: 9U x 22.5” Deep, 25” Overall Depth. The rack must be capable of supporting its
weight (69.4 kg or 153 lbs.)
Temperature:
The SPOT should be mounted in a location, where ambient temperature ranges
from -30 to +50 °C. The SPOT will limit power output at ambient temperatures above 50 °C
Clearance:
The SPOT should have at least 30 cm (12 inches) in front for airflow and access to
the cable connectors. The SPOT should have at least 15cm (6 inches) at the back to allow for
proper exhaust from the cooling fans.