Alencon BOX -V2
User Manual
31 |
P a g e
6.3 BOX System Grounding
6.3.1 JBOX Grounding – Main Earth Connection
Main earth ground must be connected to the JBOX grounding terminal.
Ground cable should be brought in through the conduit on the bottom of the cabinet
and connect to the blue Rebling terminal centered vertically on the right side of the
JBOX back – see Section 6.2.9
F
IGURE
25:
JBOX
G
ROUNDING
T
ERMINAL
6.3.2 Cabinet and Rack Grounding
A grounding terminal block is bonded to the BOX cabinet, inside the front door on the
cabinet floor (see in blue in Figure 26).
8 landing locations available on the terminal block should be used to effectively bond:
o
2 – cabinet doors
o
1 – 19” rack
o
4 – SPOT/BOSS units
o
1 – JBOX (main earth ground point)
Paint at the grounding points can be scraped away to ensure best possible contact
between conductors
F
IGURE
26:
BOX
C
ABINET
G
ROUNDING