Alencon BOX -V2
User Manual
27 |
P a g e
6.2.9 Connect Power Cables to/from BOX Cabinet, on JBOX Back
Ensure all cables are disconnected from power before handling.
Standard wiring configuration on the BOX System uses a combined Primary and combined
Secondary connection, in this case:
The Rebling terminals on the JBOX require a cable lug with an M8 clearance ID.
Rebling terminals support a maximum 4/0 AWG cable when the safety cover is used and
maximum 450 KCMIL gauge when the connection is left bare.
Connect Primary (Input) cables (Figure
21
21):
o
Primary (Input) Positive leads connect to the blue Rebling terminals on the top
right of the JBOX (Red line routed to the right)
o
Primary (Input) Negative lead connects to one of the black Rebling terminals on
the bottom right of the JBOX (Black line routed to the right)
Connect Secondary (Output) cables (Figure
21
21):
o
Secondary (Output) Positive lead connects to one of the red Rebling terminals on
the top left of the JBOX (Red line routed to the left)
o
Secondary (Output) Negative lead connects to one of the black Rebling terminals
on the bottom left of the JBOX (Black line routed to the left)
Connect Ground Cable (Figure
21
21):
o
The system ground connects to the blue Rebling terminal centered vertically on
the right side (Green line routed to the right)
Tighten each Rebling terminal with a 13mm socket. Make sure each lug is secured and
secure the cable appropriately as routed to conduit.
In cases where direct stringed connections to BOSS/SPOT units are used for a non-combined
BOX Primary or Secondary, the JBOX will have no landing location for these connectors.