F.

 

Maximum allowable working pressure (Specify Pressure): 30, 80 or 160 PSIG 
 

G.

 

U-

Type Flex Joint: The furnace must incorporate a “U

-

Type” flex joint.  The “U

-

Type” flex 

joint burner port to furnace minimizes the effects of differential stress as the boiler furnace 
expands at a greater rate than the firetubes during operation.  Boilers with other types of 
furnace to tube sheets construction are not allowed. 

 

H.

 

Front Access Door: Door to include swing joint with hinges for easy fireside access to 
combustion chamber without removal of the door. 

 

I.

 

Rear Access Door: Door to include swing joint with hinges for easy access to fireside of boiler 
without removal of the door. 

 

J.

 

Boiler Casing: The external surfaces shall be covered with a minimum of 2” mineral fiber 

insulation encased within an 18 gauge steel jacket. 

 

K.

 

Water Capacity: The boiler must be of a high mass, large volume design as listed below: 

 

Gas Input (BTUH) 

Minimum Water Capacity (Gallons) 

1,000,000 

113 

1,500,000 

113 

2,000,000 

148 

2,500,000 

215 

3,000,000 

215 

4,000,000 

280 

5,000,000 

320 

6,000,000 

440 

  

L.

 

Include the following: 
1.

 

Handholes or inspection tappings for water-side inspection. 

2.

 

Lifting lug on to of boiler. 

3.

 

Minimum 1” boiler drain valve.

 

4.

 

Minimum 1” condensate drain connection.

 

5.

 

Tappings or flanges for supply and return connections 

6.

 

Condensate Neutralizer:  Each boiler to include a factory supplied condensate 
neutralizer appropriately sized based on rated input of the boiler.  Each condensate 
neutralizer is to be field installed by installing contractor. 

 

 
2.2 WATER BOILER TRIM 
 

 

A.  Boiler to include the following factory mounted/wired: 

 

 

 

1.  Theraltimeter gauge 

 

 

 

2.  ASME relief valve 

 

 

 

3.  Operating control 

 

 

 

4.  High limit control (Manual Reset) 
5.  Modulation control 
7.

 

Probe type low water cut-off (Manual Reset) 

 

Содержание A3C-1000

Страница 1: ...ions details and attachments to other work 1 Wiring Diagrams Power signal and control wiring 2 Fuel Train Schematic 1 3 CLOSEOUT SUBMITTALS A Operation and Maintenance Data For boilers components and accessories to include in emergency operation and maintenance manuals B Warranties As specified in this section 1 4 QUALITY ASSURANCE A Electrical Components Devices and Accessories Listed and labeled...

Страница 2: ...BE CONDENSING BOILER A Basis of Design Product Subject to compliance with requirements provide products as listed 1 Aldrich Company Manufactured in Wyoming IL Model A3C B The boiler must be manufactured by a company having at least ten 10 years documented boiler manufacturing experience in accordance to ASME Section IV Boiler and Pressure Vessel Code C Description Factory packaged and firetested f...

Страница 3: ...an 18 gauge steel jacket K Water Capacity The boiler must be of a high mass large volume design as listed below Gas Input BTUH Minimum Water Capacity Gallons 1 000 000 113 1 500 000 113 2 000 000 148 2 500 000 215 3 000 000 215 4 000 000 280 5 000 000 320 6 000 000 440 L Include the following 1 Handholes or inspection tappings for water side inspection 2 Lifting lug on to of boiler 3 Minimum 1 boi...

Страница 4: ... driven by motor H Gas Train Control devices shall comply with requirements in ASME CSD 1 and UL Gas train to include pilot shut off valve regulator pilot solenoid valve intermittent electric spark pilot ignition with 100 percent main valve and pilot safety shutoff with electronic ultra violet supervision of burner flame flame rod not acceptable I Main Gas Train Factory piped and wired may be remo...

Страница 5: ...ired by code 3 Construct concrete bases 4 high and extend base not less than 6 in all directions beyond the maximum dimensions of boiler unless otherwise indicated C Install gas fired boilers according to NFPA 54 D Install electrical devices furnished with boiler but not specified to be factory mounted D Refer to drawings for additional requirements 3 3 START UP SERVICE A The mechanical contractor...

Отзывы: