Operation, Maintenance and Installation Manual

2-Zone | Outdoor Alarm System, Type 4X

VersAlarm

 4X

(Fig. 7)

Testing

Make sure all steps of the installation process are completed and there is 

power to the product. When powered, the green LEDs should illuminate. 

Test monthly to ensure system integrity.

1. To test alarm function, press and hold (1-) the test/silence

  button (Fig. 7), the red alarm LEDs should illuminate (flashing) with the

  green power/zone indicator LEDs illuminated (solid), buzzer should

  annunciate in a pulse tone, and auxiliary contacts should activate.

2. The sensors (signaling device) should be connected to the alarm

  terminals labeled ALM1 and ALM2 on the alarm circuit board. Activate

  each sensor separately, the red alarm LEDs should illuminate (flashing)

  and the green zone indicator LED should illuminate (solid) for zone-1

  (left) and zone-2 (right), buzzer should annunciate in a pulse tone, and

  the auxiliary contacts should activate.

3. To test alarm silence function, activate the sensor for zone-1 to simulate

  an alarm condition, then press/hold (1-) the test/silence button

  and the buzzer should silence while the alarm LEDs remain illuminated,

  flashing and the left green zone indicator LED should remain

  illuminated (solid). Then, deactivate the sensor, the alarm condition

  should clear and the alarm should auto reset for the next alarm cycle.

  Repeat this process for the zone-2 sensor.

4. Models with a pump terminal block, the pump should be off once power

  is applied and the pump switch is deactivated. Activate the pump switch

  and the pump should turn on. Repeat to ensure switch works properly.

Notes: Place finger in the center of the test/silence capacitive 

touch button to activate, button sensor will ignore edge touches. 

To disable the green power LEDs, press and hold the test/silence 

button for approximately 8-seconds. The green LEDs will pulse 

three times and the green power LED indicators will turn off. 

Repeat this process to turn them back on.

Содержание VersAlarm 4X

Страница 1: ...tective Equipment PPE Always wear dielectric rubber boots and other applicable protective equipment when water is on the ground or floor and you must service an energized pump alarm system or product 3 DO NOT enter the water if the water level is higher than that of the protection your PPE offers or if your PPE is not watertight 4 DO NOT use this product with or near flammable liquids 5 DO NOT ins...

Страница 2: ... auxiliary contacts is outdoor rated and powered by 120VAC or 240VAC voltage depends on model with conduit connections required When powered the green LEDs bottom middle will illuminate solid to indicate the alarm is powered and the included two level press and hold feature can disable LEDs see factory settings page 6 Install a 9VDC lithium battery for battery backup during power outages This alar...

Страница 3: ...adjust until pilot holes are lined up with the enclosure and fasten screws to secure the alarm panel in place Mounting Holes i Left to Right 1 97 center to center ii Top to Bottom 5 37 center to center 5A 5A Installation 1 Prior to mounting the alarm panel install the conduit connections required per application Open cover prior to step 2 2 Determine the center hole locations mark and drill out on...

Страница 4: ... system is ready for testing 2 The line connections from the incoming power are terminated into the respective Wago connectors terminals Fig 6A Voltage depends on model 120VAC L1 and N or 240VAC L1 and L2 3 The alarm buzzer is factory wired from the circuit board terminals to the buzzer inside the alarm panel enclosure Fig 6B 4 If connecting to an alarm security system or building automation syste...

Страница 5: ... LED should illuminate solid for zone 1 left and zone 2 right buzzer should annunciate in a pulse tone and the auxiliary contacts should activate 3 To test alarm silence function activate the sensor for zone 1 to simulate an alarm condition then press hold 1 second the test silence button and the buzzer should silence while the alarm LEDs remain illuminated flashing and the left green zone indicat...

Страница 6: ...ttery Alarm LED Indicators a The low battery alarm LEDs are factory set to off disabled The alarm panel will automatically enable the low battery alarm the first time a battery is connected The battery must be inserted for approximately one minute for the auto enable feature to activate then the green LEDs will pulse four times to indicate that the low battery alarm is enabled Note The low battery...

Отзывы: