Operation, Maintenance and Installation Manual

2-Zone | Outdoor Alarm System, Type 4X

VersAlarm

 4X

Battery Backup - Installation and Quick Test

1. To install or replace the battery for the backup power feature, open the alarm panel enclosure cover.

2. Install a 9VDC lithium battery (not included) matching the terminals on the alarm circuit board (Fig. 1A) to the terminals

  on the top of the battery. Make sure the connection is securely fastened.

3. Test to verify proper installation of the battery, the green power LEDs (bottom/middle) will not illuminate (Fig. 2) to

  conserve power. Press and hold (1-) the test/silence capacitive touch button to activate alarm test. The red alarm

  and green power/zone indicator LEDs should illuminate in quick alternating pulses (Fig. 3), buzzer should annunciate with

  four quick pulse tones matching indicators, and auxiliary contacts should activate.

Note: The LED pulse/flash functions and buzzer tone patterns are different during the testing process while on battery power versus when the incoming 

power is connected. See system testing on page 5 for testing with incoming power connected and page 6 to change factory settings for disabling LEDs.

CAUTION:

 Do not connect incoming power to the alarm panel until all steps of the installation are complete and the system is ready for testing.

WARNING!

 Lithium batteries MUST be used in any installation where the temperature can drop below 32 degrees Fahrenheit. Failure to install the proper 

battery type will cause battery failure at low temperatures and may not provide battery backup alarm protection.

(Fig. 1)

(Fig. 2)

(Fig. 3)

1A

Low Battery at 7.8 volts or Improper Installation (when powered):

The red LEDs illuminate and buzzer annunciates in sync with two quick 

pulses every 10-seconds, the auxiliary contacts will remain closed.

The VersAlarm™ 4X 2-Zone alarm panel with included auxiliary contacts is outdoor rated and powered by 120VAC or 240VAC 

(voltage depends on model) with conduit connections (required). When powered, the green LEDs (bottom/middle) will illuminate 

(solid) to indicate the alarm is powered and the included two-level press-and-hold feature can disable LEDs (see factory settings, 

page 6). Install a 9VDC lithium battery for battery backup during power outages. This alarm panel can be used for a wide variety 

of applications, including but not limited to: septic tanks, sump pits, holding tanks, pump chambers, and water tanks.

The alarm panel is equipped with audible and visual alarm indication, activated by a normally open or normally closed sensor wired 

to the quick connect terminals for monitoring two zones. A variety of sensors can be used such as a float switch, pressure switch, 

or any "dry" type sensor that "closes" during an alarm condition (normally open or normally closed). Use the auxiliary contacts to 

connect to building automation systems (BAS) and phone dialers.

An alarm condition occurs when the sensor (signaling device) contact is activated for zone-1 and/or zone-2, during which the red 

alarm LEDs will illuminate (flashing) with the green LED illuminated (solid) for zone-1 (left) and/or zone-2 (right) alarm indication, 

buzzer will annunciate with a pulse tone, and auxiliary contacts will activate. The alarm condition will stay on until the sensor for 

zone-1 and/or zone-2 is deactivated. Press and hold (1-) the test/silence capacitive touch button to silence the buzzer 

during an alarm condition, the alarm LEDs remain illuminated, flashing. The silence condition will reset when the sensor for zone-1 

and/or zone-2 deactivates and the alarm will auto reset for the next alarm cycle. Test alarm monthly to ensure system integrity, 

press and hold (1-) the test/silence button, the red alarm LEDs should illuminate (flashing), buzzer should annunciate with 

a pulse tone, and auxiliary contacts should activate.

Description of Operation

Note: If zone-1 is in an alarm condition and the buzzer is silenced, and then zone-2 goes into an alarm condition, the buzzer will reactivate until the test/silence 

capacitive touch button is pressed to acknowledge that a new alarm condition has occurred.

Содержание VersAlarm 4X

Страница 1: ...tective Equipment PPE Always wear dielectric rubber boots and other applicable protective equipment when water is on the ground or floor and you must service an energized pump alarm system or product 3 DO NOT enter the water if the water level is higher than that of the protection your PPE offers or if your PPE is not watertight 4 DO NOT use this product with or near flammable liquids 5 DO NOT ins...

Страница 2: ... auxiliary contacts is outdoor rated and powered by 120VAC or 240VAC voltage depends on model with conduit connections required When powered the green LEDs bottom middle will illuminate solid to indicate the alarm is powered and the included two level press and hold feature can disable LEDs see factory settings page 6 Install a 9VDC lithium battery for battery backup during power outages This alar...

Страница 3: ...adjust until pilot holes are lined up with the enclosure and fasten screws to secure the alarm panel in place Mounting Holes i Left to Right 1 97 center to center ii Top to Bottom 5 37 center to center 5A 5A Installation 1 Prior to mounting the alarm panel install the conduit connections required per application Open cover prior to step 2 2 Determine the center hole locations mark and drill out on...

Страница 4: ... system is ready for testing 2 The line connections from the incoming power are terminated into the respective Wago connectors terminals Fig 6A Voltage depends on model 120VAC L1 and N or 240VAC L1 and L2 3 The alarm buzzer is factory wired from the circuit board terminals to the buzzer inside the alarm panel enclosure Fig 6B 4 If connecting to an alarm security system or building automation syste...

Страница 5: ... LED should illuminate solid for zone 1 left and zone 2 right buzzer should annunciate in a pulse tone and the auxiliary contacts should activate 3 To test alarm silence function activate the sensor for zone 1 to simulate an alarm condition then press hold 1 second the test silence button and the buzzer should silence while the alarm LEDs remain illuminated flashing and the left green zone indicat...

Страница 6: ...ttery Alarm LED Indicators a The low battery alarm LEDs are factory set to off disabled The alarm panel will automatically enable the low battery alarm the first time a battery is connected The battery must be inserted for approximately one minute for the auto enable feature to activate then the green LEDs will pulse four times to indicate that the low battery alarm is enabled Note The low battery...

Отзывы: