Operation, Maintenance and Installation Manual

2-Zone | Outdoor Alarm System, Type 4X

VersAlarm

 4X

Factory Settings and Functions

The VersAlarm™ 4X comes standard from the factory with the settings listed in this section. Review the operation and 

settings information below, reference when required to disable LEDs or for troubleshooting purposes.

1. When powered, the green LEDs (Fig. 8; bottom/middle) will illuminate (solid) to indicate the alarm is powered. The power

  LEDs are factory set to be on (solid) and will pulse when disabling this feature.

2. The red alarm LEDs (Fig. 9; top/bottom/left/right) will illuminate during a liquid level alarm condition (flashing) for zone-1

  and/or zone-2 and for a low battery alarm at 7.8 volts or improper battery installation (quick pulse).

(Fig. 8)

3. Green Power On LED Indicators:

   

a.  Factory set to “on” (illuminate/solid).

   

b.  Disable by pressing and holding the test/silence capacitive touch button for approximately 8-seconds, the green

   

  LEDs will pulse three times and the green power LED indicators will turn off. Repeat this process to turn them

   

  back on.

4. Red Low Battery Alarm LED Indicators:

   

a.  The low battery alarm LEDs are factory set to “off” (disabled). The alarm panel will automatically enable the low

   

  battery alarm the first time a battery is connected. The battery must be inserted for approximately one-minute for

   

  the auto-enable feature to activate, then the green LEDs will pulse four times to indicate that the low battery alarm

   

  is enabled.

Note: The low battery alarm feature is automatically enabled only after a battery is connected for the first time. The alarm feature must then be manually 

enabled or disabled.

   

c.  Disable low battery alarm LEDs by pressing and holding the test/silence capacitive touch button for approximately

   

  16-seconds, the green LEDs will quick pulse five times to indicate the low battery alarm has been disabled.

   

d.  Enable low battery alarm LEDs by pressing and holding the test/silence capacitive touch button for approximately

   

  16-seconds, the green LEDs will quick pulse five times and then the green LEDs will pulse five times upon release

   

  of the button to indicate the low battery alarm has been enabled.

Note: When the system is running on battery backup power and the low battery alarm is disabled, the low battery alarm will temporarily re-activate to 

indicate when the battery is about to lose its charge. The settings will return to the last programmed state upon full power being restored.

Note: The LED settings cannot be changed while the system is running on battery backup power.

(Fig. 9)

Содержание VersAlarm 4X

Страница 1: ...tective Equipment PPE Always wear dielectric rubber boots and other applicable protective equipment when water is on the ground or floor and you must service an energized pump alarm system or product 3 DO NOT enter the water if the water level is higher than that of the protection your PPE offers or if your PPE is not watertight 4 DO NOT use this product with or near flammable liquids 5 DO NOT ins...

Страница 2: ... auxiliary contacts is outdoor rated and powered by 120VAC or 240VAC voltage depends on model with conduit connections required When powered the green LEDs bottom middle will illuminate solid to indicate the alarm is powered and the included two level press and hold feature can disable LEDs see factory settings page 6 Install a 9VDC lithium battery for battery backup during power outages This alar...

Страница 3: ...adjust until pilot holes are lined up with the enclosure and fasten screws to secure the alarm panel in place Mounting Holes i Left to Right 1 97 center to center ii Top to Bottom 5 37 center to center 5A 5A Installation 1 Prior to mounting the alarm panel install the conduit connections required per application Open cover prior to step 2 2 Determine the center hole locations mark and drill out on...

Страница 4: ... system is ready for testing 2 The line connections from the incoming power are terminated into the respective Wago connectors terminals Fig 6A Voltage depends on model 120VAC L1 and N or 240VAC L1 and L2 3 The alarm buzzer is factory wired from the circuit board terminals to the buzzer inside the alarm panel enclosure Fig 6B 4 If connecting to an alarm security system or building automation syste...

Страница 5: ... LED should illuminate solid for zone 1 left and zone 2 right buzzer should annunciate in a pulse tone and the auxiliary contacts should activate 3 To test alarm silence function activate the sensor for zone 1 to simulate an alarm condition then press hold 1 second the test silence button and the buzzer should silence while the alarm LEDs remain illuminated flashing and the left green zone indicat...

Страница 6: ...ttery Alarm LED Indicators a The low battery alarm LEDs are factory set to off disabled The alarm panel will automatically enable the low battery alarm the first time a battery is connected The battery must be inserted for approximately one minute for the auto enable feature to activate then the green LEDs will pulse four times to indicate that the low battery alarm is enabled Note The low battery...

Отзывы: