EC3-33x Coldroom Controller with EX5

User Manual

EC3-33x

A.6.5.063E - Rev 4

7

Emerson Electric GmbH & Co  -  ALCO CONTROLS  -  Heerstr. 111  -  D-71332 Waiblingen  -  Germany - Tel.: ..49 (0) 7151 509 0 - Fax: 49 (0) 7151 509 200

TECHNICAL SPECIFICATIONS

Temperature ranges:
Sensor                     -50 / +50°C     or -58/+122°F
Enclosure
Operating

0 / +50°C  

or 32 / +122°F

Storage

-10 / +70°C  or 14 / +158°F

Power supply:

24V AC, -15%, +10%

Consumption:

12 VA

Case:
Controller:

Aluminum 255 x 100 x  65 mm

Display:

Auto extinguishing Plastic, 75 x 33 x 73 mm

Mounting:
Controller;

DIN rail

Display:

Panel mounting

Connections:

Plug in connectors for cables of max. 1.5
mm

2

,

min. 0.5 mm

section

Display:

2½ digits

Indicators LED:

Compressor, Fan, Defrost heater, IR
activated, ALARM , Neuron ID

Inputs:

Compressor failure, Door contact, Switch 1,
Switch 2, oil in, oil out, Air in temp., Air out
temp., Defrost termination temp., Temp. # 6

Switch

24V  AC / DC or 230V AC

Sensor:

NTC ( 10K  at 25°C )

Pressure Sensor:

PT3-07 4- 20 mA

Outputs:

Relays SPDT
I

max

 = 8A res (2A), VAC max = 250V

TRIAC
I

max

 = 4A, VAC max = 250V

Stepper motor
I

max

 = 0.7A, VDC = 24V

Environmental pollution non aggressive atmosphere
Protection class

IP65 (frontal protection with gasket)

Insulation

class II

Important:

 Keep controller and sensor lines separated from

mains cable  with at least 3 cm.

SAFETY STANDARD
In order to comply the safety standard (CEI 107-70) see the following:
1)  Connection cables should be suitable for 90°C operation;

2)  

Class II transformers 24 VAC double insulated must be used

3)  

Aluminum case must be connected to ground

DIMENSIONS

Housing Dimensions EC3-33x Controller

250

62

72

104

EC3

Housing Dimensions ECD-001 Display Unit

78

36

6

36.5

Cutout 71 x 29 mm

Содержание EC3-33x

Страница 1: ...EC3 33x User Manual Rev 4 14 01 2003...

Страница 2: ...ill return to the by 1 selected data NEURON ID SERVICE BUTTON Display Press the button for app 1 second to send the Neuron ID An LED in the left upper corner will indicate the transmission of the Neur...

Страница 3: ...1 flag 1 d3 Pulsed defrost 0 1 flag 0 d4 Defrost at power up 0 1 flag 0 d5 Delay for power up defrost 0 180 min 0 d6 Pump down delay 0 180 sec 0 d7 Drain delay 0 180 min 2 d8 Injection delay 0 180 se...

Страница 4: ...in and air out sensor monitoring off temp alarms will be generated A0 Mean factor alarm temperature r8 Mean factor day operation r9 Mean factor night operation Temperature calculation by the followin...

Страница 5: ...eaning 0 off 1 on u0 Refrigerant 0 R22 1 R134a 2 R507 3 R404A 4 R407C u1 Correction Glide positive Values Pressure drop negative Values u2 MOP Control 0 off 1 on u4 Control Mode 0 off 1 fixed superhea...

Страница 6: ...n failure by time or temperature Ft Fan start up failure by time or temperature Ab external battery alarm external battery indicates an alarm MESSAGES No data The display will show an at node start up...

Страница 7: ...ressor failure Door contact Switch 1 Switch 2 oil in oil out Air in temp Air out temp Defrost termination temp Temp 6 Switch 24V AC DC or 230V AC Sensor NTC 10K at 25 C Pressure Sensor PT3 07 4 20 mA...

Страница 8: ...BL BK WH Battery Fail 24V AC Fan DI 1 8 24V AC DC or 230V AC DI 9 12 24V AC DC only DO 250V max 8A 2A Comp Heater Alarm Relay Door Comp safety Di3 Di4 Do1 1 C 2 Do2 1 C 2 Do3 1 C 2 Do4 1 C 2 LON A B...

Страница 9: ...sensors is between 9 and 3 o clock as shown on the picture The air sensors must be mounted on spacers in the middle of the air duct so that the air flow around The recommended positions in detail 1 S1...

Страница 10: ...nding on cable type Transfer rate 39 kbits s FTT10 Structure free topology Termination RC Network Medium Twisted pair 2 wires Connection 11 12 Data 13 free Nodes Segment 64 Units Cable length max 2700...

Страница 11: ...0 7151 509 0 Fax 49 0 7151 509 200 NODE OBJECTS The EC3 33x coldroom controller has 11 LonMark Objects EC3 33x Node Object Compressor Object 20004 Display Object 20006 Analog Sensor Object 20008 Evapo...

Страница 12: ...all objects in the node to normal operation RQ_DISABLED This requested object is disabled output network variable of the object will not longer be updated The object will not reacted on input network...

Страница 13: ...ostat object SNVT_temp_p nvoAlarmAirTemp O Alarm temperature used by thermostat object SNVT_temp_p nvoAirOutTemp O Air out sensor temperature SNVT_temp_p nvoAirInTemp O Air in sensor temperature SNVT_...

Страница 14: ...on unsigned short MeanNight 0 100 50 y y y 5 17 rd Difference day operation unsigned short DiffDay K 0 1 20 2 0 1 y y y Diff between cut in cut out 18 St Setpoint day operation signed long SpDay C r1...

Страница 15: ...oDefrTemp O Currently used defrost termination temperature SNVT_lev_disc nvoHeater O Status of the defrost heater SNVT_lev_disc nviStartUp I Input to terminate a synchronized defrost ST_ON will start...

Страница 16: ...14 dI Def r ost t i m ei nt er val unsi gnedshor t I nt er val Ti m e h 0 192 8 y y y Ti m e i nt er v al bet ween t w odef r ost cycl es 15 dU St ar t up del ay unsi gnedshor t St ar t UpDl y m i n...

Страница 17: ...l control 8 1 Termination error Configuration Parameters Fan UNVT_FAN Code Description Variable type Name Unit Min Max Default Res IR Kb Lon 0 F1 Fan startup sequence after defrost unsigned short Star...

Страница 18: ...ct SNVT_lev_disc nviCompSafety Failure input for compressor safety ST_ON compressor off and locked UNVT_COMP nciCompCnfg C Configuration parameters of the fan object The network variable nvoCompStatus...

Страница 19: ...pad unsigned short IrKb 0 3 3 y y y 1 1 H3 IR access code unsigned short IRCode 0 199 0 y y y 2 H5 Password unsigned short PassWord 0 199 12 y y y 3 1 Value to be shown unsigned short Data 0 11 0 y y...

Страница 20: ...ircuit E2 6 Air out sensor open E3 7 Air out sensor short circuit E3 8 Defrost termination sensor open E4 9 Defrost termination sensor short circuit E4 10 Temperature 6 sensor open E5 11 Temperature 6...

Страница 21: ...perheat object SNVT_temp_p nvoEvapOutTemp O Currently used coil out temperature of the superheat object SNVT_switch nviForcedValve I Manual control of the valve output SNVT_temp_p nvoSuperheatRef O Cu...

Страница 22: ...n n y 5 9 uu Start up opening unsigned short Opening 50 100 100 y y y 10 ut Valve type unsigned short ValveType 0 3 0 y y y 7 11 Data source unsigned short Sensor 0 31 0 n n y 6 Total 13 bytes 1 0 R2...

Страница 23: ...trols the relays and the TRIAC If the object is disabled the object will not react on any network variable update and the digital outputs will stay unchanged Network Variables Variable Type Name Type...

Отзывы: