EC3-33x Coldroom Controller with EX5

User Manual

EC3-33x

A.6.5.063E - Rev 4

2

Emerson Electric GmbH & Co  -  ALCO CONTROLS  -  Heerstr. 111  -  D-71332 Waiblingen  -  Germany - Tel.: ..49 (0) 7151 509 0 - Fax: 49 (0) 7151 509 200

The EC3-33x coldroom controller is a universal controller for
refrigeration applications with an electronic stepper motor
expansion valve like the EX5. The controller has six
temperature inputs for coil in, coil out, air in, air out and defrost
termination temperatures. The sixes temperature input is a
universal temperature input. For measurement of  the saturation
pressure a PT3 pressure sensor with 4 – 20 mA interface can
be connected to the controller. The controller has four relay
outputs, one defined for compressor control, one defined for
defrost heater control, one defined for an alarm output and one
as a universal relay output. The TRIAC outputs is defined for
fan control. The TRIAC can drive 24V / 230V 4A. The controller
has four digital inputs for 24V AC/ DC or 230V AC. One input is
defined for compressor failure, one input is defined for a door
contact and two inputs are free for universal purpose. The
stepper motor interface can drive stepper motor with 24V DC
and 0.7 A. The optional display can show values with a decimal
point in the range between -19.9 and +19.9°C otherwise without
decimal point. An IR receiver for the optional IR remote control
unit is build in. For communication purposes, an Echelon
LONWorks interface is installed. Two transceiver types are
available RS485 or FTT10A.  The supply voltage is 24 VAC.
Transformers for 230V or 110V mains supply are available as
options.

DISPLAY  ECD-001:

The data to be shown on the display can be selected by the user.
In case of on alarm, the alarm code is displayed alternately with the
selected data. The alarm code can be inhibited by the user. To
scroll through all possible displayable data press the SEL button.
The display will show for one second the numerical identifier of the
data and then the selected data. After two minutes the display will
return to the by /1 selected data.

NEURON ID / SERVICE BUTTON:

 Display :

Press the   button for app. 1 second to send the Neuron ID.
An LED in the left upper corner will indicate the transmission
of the Neuron ID.
Controller:
There is a small hole left of the network connector. Use a
small pen or screwdriver to press the switch behind the hole.
An LED close to the switch will light to indicate the
transmission of the Neuron ID.

LOAD DEFAULT PARAMETERS:

  Use a small pen or screwdriver to press the service pin switch

on the controller  and switch on the power supply on. The
EC3-21x will be reset to default parameters.

PARAMETERS:

The configuration parameters are protected by a numerical
password. The default password is “12”. To select the
parameter configuration :

  Press the PRG button for more than 5 seconds

  A flashing 0 is displayed

 Press   or   until 12 is displayed; (password)

  Press SEL to confirm password

  The first modifiable parameter code is displayed (/1).

  To modify parameters see Parameters modification below.

PARAMETER MODIFICATION:

 Press   or   to show the code of the parameter that has to

be changed;

  Press SEL to display the selected parameter value;

 Press   or   to increase or decrease the value;

  Press SEL to temporally confirm the new value and display its

code;
Repeat the procedure from the beginning "

press 

 or 

to

show...

"

To exit modifying the parameters with the new values:

  Press PRG to confirm the new values and exit the parameters

modification procedure.

To exit without modifying any parameter:

  Do not press any button for at least 60 seconds (TIME OUT).

  Press “ESC” on IR remote control.

DEFROST ACTIVATION:

A defrost cycle can be activated locally from the keypad :

 Press the   button for more than 5 seconds

  A flashing 0 is displayed

 Press   or   until 12 is displayed; (password)

  Press SEL to confirm password

  The defrost cycle is activated

CLEAR ALARMS:

A defrost termination or fan activation alarm can be cleared
from the keypad :

 Press   or   for more than 5 seconds.

  “CL” will be shown in the display to indicate that the

alarms are cleared.

INDICATIONS ON THE DISPLAY :

COMPRESSOR

Logical status of the compressor
relay

FAN

Logical status of the fan relay

DEFROST

Logical status of the defrost heater
relay

ALARM

Alarm condition

 

Содержание EC3-33x

Страница 1: ...EC3 33x User Manual Rev 4 14 01 2003...

Страница 2: ...ill return to the by 1 selected data NEURON ID SERVICE BUTTON Display Press the button for app 1 second to send the Neuron ID An LED in the left upper corner will indicate the transmission of the Neur...

Страница 3: ...1 flag 1 d3 Pulsed defrost 0 1 flag 0 d4 Defrost at power up 0 1 flag 0 d5 Delay for power up defrost 0 180 min 0 d6 Pump down delay 0 180 sec 0 d7 Drain delay 0 180 min 2 d8 Injection delay 0 180 se...

Страница 4: ...in and air out sensor monitoring off temp alarms will be generated A0 Mean factor alarm temperature r8 Mean factor day operation r9 Mean factor night operation Temperature calculation by the followin...

Страница 5: ...eaning 0 off 1 on u0 Refrigerant 0 R22 1 R134a 2 R507 3 R404A 4 R407C u1 Correction Glide positive Values Pressure drop negative Values u2 MOP Control 0 off 1 on u4 Control Mode 0 off 1 fixed superhea...

Страница 6: ...n failure by time or temperature Ft Fan start up failure by time or temperature Ab external battery alarm external battery indicates an alarm MESSAGES No data The display will show an at node start up...

Страница 7: ...ressor failure Door contact Switch 1 Switch 2 oil in oil out Air in temp Air out temp Defrost termination temp Temp 6 Switch 24V AC DC or 230V AC Sensor NTC 10K at 25 C Pressure Sensor PT3 07 4 20 mA...

Страница 8: ...BL BK WH Battery Fail 24V AC Fan DI 1 8 24V AC DC or 230V AC DI 9 12 24V AC DC only DO 250V max 8A 2A Comp Heater Alarm Relay Door Comp safety Di3 Di4 Do1 1 C 2 Do2 1 C 2 Do3 1 C 2 Do4 1 C 2 LON A B...

Страница 9: ...sensors is between 9 and 3 o clock as shown on the picture The air sensors must be mounted on spacers in the middle of the air duct so that the air flow around The recommended positions in detail 1 S1...

Страница 10: ...nding on cable type Transfer rate 39 kbits s FTT10 Structure free topology Termination RC Network Medium Twisted pair 2 wires Connection 11 12 Data 13 free Nodes Segment 64 Units Cable length max 2700...

Страница 11: ...0 7151 509 0 Fax 49 0 7151 509 200 NODE OBJECTS The EC3 33x coldroom controller has 11 LonMark Objects EC3 33x Node Object Compressor Object 20004 Display Object 20006 Analog Sensor Object 20008 Evapo...

Страница 12: ...all objects in the node to normal operation RQ_DISABLED This requested object is disabled output network variable of the object will not longer be updated The object will not reacted on input network...

Страница 13: ...ostat object SNVT_temp_p nvoAlarmAirTemp O Alarm temperature used by thermostat object SNVT_temp_p nvoAirOutTemp O Air out sensor temperature SNVT_temp_p nvoAirInTemp O Air in sensor temperature SNVT_...

Страница 14: ...on unsigned short MeanNight 0 100 50 y y y 5 17 rd Difference day operation unsigned short DiffDay K 0 1 20 2 0 1 y y y Diff between cut in cut out 18 St Setpoint day operation signed long SpDay C r1...

Страница 15: ...oDefrTemp O Currently used defrost termination temperature SNVT_lev_disc nvoHeater O Status of the defrost heater SNVT_lev_disc nviStartUp I Input to terminate a synchronized defrost ST_ON will start...

Страница 16: ...14 dI Def r ost t i m ei nt er val unsi gnedshor t I nt er val Ti m e h 0 192 8 y y y Ti m e i nt er v al bet ween t w odef r ost cycl es 15 dU St ar t up del ay unsi gnedshor t St ar t UpDl y m i n...

Страница 17: ...l control 8 1 Termination error Configuration Parameters Fan UNVT_FAN Code Description Variable type Name Unit Min Max Default Res IR Kb Lon 0 F1 Fan startup sequence after defrost unsigned short Star...

Страница 18: ...ct SNVT_lev_disc nviCompSafety Failure input for compressor safety ST_ON compressor off and locked UNVT_COMP nciCompCnfg C Configuration parameters of the fan object The network variable nvoCompStatus...

Страница 19: ...pad unsigned short IrKb 0 3 3 y y y 1 1 H3 IR access code unsigned short IRCode 0 199 0 y y y 2 H5 Password unsigned short PassWord 0 199 12 y y y 3 1 Value to be shown unsigned short Data 0 11 0 y y...

Страница 20: ...ircuit E2 6 Air out sensor open E3 7 Air out sensor short circuit E3 8 Defrost termination sensor open E4 9 Defrost termination sensor short circuit E4 10 Temperature 6 sensor open E5 11 Temperature 6...

Страница 21: ...perheat object SNVT_temp_p nvoEvapOutTemp O Currently used coil out temperature of the superheat object SNVT_switch nviForcedValve I Manual control of the valve output SNVT_temp_p nvoSuperheatRef O Cu...

Страница 22: ...n n y 5 9 uu Start up opening unsigned short Opening 50 100 100 y y y 10 ut Valve type unsigned short ValveType 0 3 0 y y y 7 11 Data source unsigned short Sensor 0 31 0 n n y 6 Total 13 bytes 1 0 R2...

Страница 23: ...trols the relays and the TRIAC If the object is disabled the object will not react on any network variable update and the digital outputs will stay unchanged Network Variables Variable Type Name Type...

Отзывы: