Configuration Parameters
Superheat
UNVT_EVAPORATOR
Code
Description
Variable type
Name
Unit
Min
Max
Default
Res.
IR
Kb
Lon
0
u0
Refrigerant
unsigned short Refrig
0
4
3
y
y
y
*1
1
u1
Correction
signed long
Corr
K
-20
20
0
0.1
y
y
y
*2
2
u2
MOP Control
unsigned short MOP
0
1
0
y
y
y
*3
3
u3
MOP temperature
signed short
MOPTemp
°C
-40
40
0
y
y
y
4
u4
Control mode
unsigned short Mode
0
2
1
y
y
y
*4
5
u5
Super heat reference init
unsigned short RefInit
K
u6
u7
6
y
y
y
6
u6
Super heat reference min unsigned short RefMin
K
3
u7
3
y
y
y
7
u7
Super heat reference max unsigned short RefMax
K
u6
20
15
y
y
y
8
u8
Saturation Temperatur
unsigned short SatTemp
0
1
0
n
n
y
*5
9
uu
Start up opening
unsigned short Opening
%
50
100
100
y
y
y
10
ut
Valve type
unsigned short ValveType
0
3
0
y
y
y
*7
11
Data
source
unsigned
short Sensor
0
31
0
n
n
y
*6
Total 13 bytes
*1
0 = R22
1 = R134a
2 = R507
3 = R404A
4 = R407C
*2 Glide = + Values
Pressure drop = - Values
*3 0
=
Off
1 = On
*4
0 = Off
1 = fixed superheat
2 = adaptive superheat
*5
0 = Temperature
1 = Pressure
*6
Sensor = E A Med Pressure
EvapIn
0 = Internal
1 = LON network
EvapOut
0 = Internal
2 = LON network
AirTemp
0 = Internal
4 = LON network
MediaTemp
0 = Internal
8 = LON network
Pressure
0 = Internal
16 = LON network
*7
Valve type ( only stepper motor valves)
0 = EX5
1 = EX6
2 = EX7
3 = EX8
Alarm Messages
Alarm messages will be send by the “nvoAlarm” of the node object.
Condition
SNVT #
Alarm Value
Message
Priority
Any internal alarm occurs
83
nvoEvapStatus
AL_ALM_CONDITION
PR_LEVEL_3
Any internal alarm disappears
83
nvoEvapStatus
AL_NO_CONDITION
PR_LEVEL_0
External alarm occurs
22
nviSystemFailure
AL_ALM_CONDITION
PR_LEVEL_3
External alarm disappears
22
nviSystemFailure
AL_NO_CONDITION
PR_LEVEL_0
Содержание EC3-33x