EC3-33x Coldroom Controller with EX5
User Manual
EC3-33x
A.6.5.063E - Rev 4
6
Emerson Electric GmbH & Co - ALCO CONTROLS - Heerstr. 111 - D-71332 Waiblingen - Germany - Tel.: ..49 (0) 7151 509 0 - Fax: 49 (0) 7151 509 200
ALARMS AND MESSAGES
ALARM CODES
E0
Coil in sensor failure
E1
Coil out sensor failure
E2
Air in sensor failure
E3
Air out sensor failure
E4
Defrost termination sensor failure
E5
Temp. 6 sensor failure
E6
Pressure sensor failure
•
No sensor connected.
•
The sensor cable is broken or short circuited.
Er
Data error
•
Data send to the display is out of range.
Ad
Door open alarm
AH
High temperature alarm
AL
Low temperature alarm
AE
Thermostat emergency operation
•
Air in and air out sensor failure
AF
Superheat, external system failure
•
External failure input is active
Ao
Superheat, emergency operation
•
Sensor failure
Ar
Superheat, no refrigerant flow
•
No refrigerant flow was detected
Au
Superheat, Valve opening 100%
•
Valve at 100 % opening for more then 2 minutes
dt
Defrost termination failure by time or
temperature
Ft
Fan start-up failure by time or
temperature
Ab
external battery alarm
•
external battery indicates an alarm
MESSAGES
---
No data
•
The display will show an “---” at node start up and when no
data is send to the display.
In
Configuration data initialization
•
The display will show an “In” when the configuration data
are initialized with the factory default values.
Id
Wink request received
•
The display will show a flashing “Id” when the wink request
was received. The flashing “Id” will be shown on the display
until the service button will be pressed, or a 30 min delay
timer will expire or a second wink request will be received
by the node.
OF
Offline
•
The node is offline, no application is running. This is the
result of a network management command an will happen
for example during node installation.
oF
Digital input status
on
Digital input status
•
Indication of the digital inputs, of = switch open, on = switch
closed
dS
Defrost standby
dP
Defrost pump down
df
Defrost cycle
dd
Defrost drain delay
dI
Defrost injection delay
du
Defrost start up delay
Cn
Cleaning
CL
Alarms are cleared
N.B. When cleaning the display use damp cloth and neutral
detergent.