Quick Start Guide

 

AlarmSense Quick Start Guide

 

Document Ref: EUFS-UI-ALS-02 Issue 1.0

 

3

 

 

 

 

PROGRAMMING OPTIONS - SEE FULL MANUAL FOR FURTHER DETAILS

 

 

Option/Setting

 

Initialise Factory Settings

 

Description

 

Restores all programming, test modes and disablements back to 
factory default settings

 

Code(s)

 

 

1113

 

Set Fault Buzzer Volume

 

Set the fault buzzer volume to high or low

 

2224

 

Disable Buzzer In Test Mode

 

Prevent the sounding of the panel buzzer during test mode

 

2223

 

Set Keypad Entry Code

 

Change/remove the keypad access code

 

2123

 

EN54 Sounder Resound Options

 

Set zones to not resound alarms after an initial fire condition

 

1114

 

AlarmSense Programming 
Options

 

• Set non priority zones

 

• Set alarm confirmation time, 30, 60 or 120 seconds

 

• Set non priority indication, yes or no

 

 

1212

 

Zone Function Settings

 

• Set zone to latching or non latching

 

• Set zone to old B.S (short circuit = fire)

 

 

3121

 

Common Fire Outputs

 

Set the common fire outputs to cancel on Silence Alarms

 

4242

 

Conventional Sounder Circuit 
Function Options

 

Change the default panel sounder circuit responses to ‘Silence 
Alarms’, ‘Evacuate’, ‘Class Change’ and ‘Alert’

 

 

4344

 

Содержание Pulse2

Страница 1: ...EN54 APPROVED 2 4 ZONE PULSE2 ALARMSENSE CONTROL PANEL 810a 05 Document Ref EUFS UI ALS 02 Issue 1 0...

Страница 2: ...accordance with this manual Hazardous voltages are present inside the panel DO NOT open it unless you are qualified and authorised to do so There is no need to open the panel s enclosure except to car...

Страница 3: ...capacity are capable of delivering very high currents which can cause fire or injury therefore battery connections should be done with caution The panel is supplied with battery leads already connecte...

Страница 4: ...nse panels have special programming options incorporated for use with AlarmSense devices Setting as to whether non priority mode is available per zone Programmable time delay for non priority alarms 3...

Страница 5: ...e 2223 Set Keypad Entry Code Change remove the keypad access code 2123 EN54 Sounder Resound Options Set zones to not resound alarms after an initial fire condition 1114 AlarmSense Programming Options...

Страница 6: ...switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off...

Страница 7: ...tton once more will move the selection back to Zone 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the ind...

Страница 8: ...ore will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to...

Страница 9: ...The following table shows details of the indications in fault diagnosis mode Disable Mode Test Mode LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing...

Страница 10: ...rt Guide Document Ref EUFS UI ALS 02 Issue 1 0 8 SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DATE DEVICE TESTED LOCATION COMMENTS IF ANY INITIALS OF...

Страница 11: ...eck to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the green RESET button fig 3 T...

Страница 12: ...EU Fire Security Units 2 4 The Pavilions Bridgefold Road Rochdale OL11 5BY...