background image

Quick Start Guide

 

AlarmSense Quick Start Guide

 

Document Ref: EUFS-UI-ALS-02 Issue 1.0

 

1

 

 

 

 

 

MAINS CONNECTIONS

 

Do not connect the mains supply to the panel 
until  you  are  fully  conversant  with  the  layout 
and features of the equipment.

 

 

A rating  plate  is attached to the power supply 
module  describing  the  nature  of  the  supply 
permitted.

 

 

The incoming mains supply should be brought 
into  the  panel  via  one  of  the  knockouts 
provided.

 

 

A suitable cable gland must be used to secure 
the  outer  sheath  of  the  cable  used.  The  earth 
must  first  be  connected  to  the  primary  earth 
stud (peg) marked  with a 

symbol, using

 

the ring crimp provided. 

 

Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the 
terminal block while leaving the earth connection intact.

 

 

 

CONNECTING THE BATTERIES

 

Batteries of even very small capacity are capable of delivering very high currents which can cause fire or 
injury, therefore battery connections should be done with caution.

 

 

The panel is supplied with battery leads already connected to the battery terminals on the main PCB. 
These leads are coloured red for +ve and black for -ve.

 

 

2 x 12v batteries should be connected in series 
using  the  white  jumper  lead  provided.  See 
diagram.

 

 

To optimise the service life of  the  batteries,  the 
battery  charger  output  voltage  varies  with 
temperature.

 

 

N.B.

 

In the event of mains failure, the battery charger 
circuit will protect the batteries from full discharge 
by  disconnecting  them  when  they  reach  below 
19v.  When  the  mains  supply  is  restored  the 
batteries will be automatically reconnected.

 

 
 

 

NOTE:

 

If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute 
until the monitoring cylce has finished polling. This is normal. If the fault 

doesn’t clear after 1 minute, check 

connections.

 

O N

 

+  -  

 

BATTERY

 

1 2 3

 

-ve

 

+ve

 

 

 

12v SLA Battery

 

 
 

12v SLA Battery

 

V+

 

V

E

 

N

 

L

 

Содержание Pulse2

Страница 1: ...EN54 APPROVED 2 4 ZONE PULSE2 ALARMSENSE CONTROL PANEL 810a 05 Document Ref EUFS UI ALS 02 Issue 1 0...

Страница 2: ...accordance with this manual Hazardous voltages are present inside the panel DO NOT open it unless you are qualified and authorised to do so There is no need to open the panel s enclosure except to car...

Страница 3: ...capacity are capable of delivering very high currents which can cause fire or injury therefore battery connections should be done with caution The panel is supplied with battery leads already connecte...

Страница 4: ...nse panels have special programming options incorporated for use with AlarmSense devices Setting as to whether non priority mode is available per zone Programmable time delay for non priority alarms 3...

Страница 5: ...e 2223 Set Keypad Entry Code Change remove the keypad access code 2123 EN54 Sounder Resound Options Set zones to not resound alarms after an initial fire condition 1114 AlarmSense Programming Options...

Страница 6: ...switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off...

Страница 7: ...tton once more will move the selection back to Zone 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the ind...

Страница 8: ...ore will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to...

Страница 9: ...The following table shows details of the indications in fault diagnosis mode Disable Mode Test Mode LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing...

Страница 10: ...rt Guide Document Ref EUFS UI ALS 02 Issue 1 0 8 SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DATE DEVICE TESTED LOCATION COMMENTS IF ANY INITIALS OF...

Страница 11: ...eck to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the green RESET button fig 3 T...

Страница 12: ...EU Fire Security Units 2 4 The Pavilions Bridgefold Road Rochdale OL11 5BY...

Отзывы: