Thermostat Z-Wave Specification

 

June 26, 2019 

 

Building 36 Technologies 

An Alarm.com Company 

 

 

15 

 

5.1.47

 

0x2F : RESERVED 

5.1.48

 

0x30 : PIR Enable 

 

Default is enabled. 

 

Size 1 byte 

5.1.49

 

0x31 : Display Options 

 

Bitmask to set display options. 

o

 

Bit 0 

 

if ‘1’, show humidity on the main screen in all modes.

 

 

Default is 0x00 

 

Size 1 byte 

5.1.50

 

0x32 : System Configuration (READ ONLY) 

 

Summarized report of system configuration 

Bits 

Loads 
State 

Aux Fan  Cool Stages 

Heat Stages 

Fuel 

HVAC Type 

Z2 Configuration 

Z1 Configuration 

Reserved 

Override 

Reserved 

 

HVAC Type : 00b 

 Normal, 01b 

 Heat Pump 

 

Fuel : 0b 

 Fuel, 1b -Electric 

 

Aux Fan : 0b- Disabled, 1b 

 Enabled 

 

Override :  1b 

 Relays manually configured, 0b 

 Relays automatically detected 

 

Size 4 bytes 

5.1.51

 

0x33 : Thermostat Reset (Write Only) 

 

Must write the magic value 0x0B36 to take effect. 

 

Size 2 byte 

5.1.52

 

0x34 : Vent Options 

 

0x00 

 Disabled 

 

0x01 

 Always activate regardless of thermostat operating state 

 

0x02 

 Only activate vent when the thermostat operating state is heating. 

 

0x03 

 Only activate vent when the thermostat operating state is cooling. 

 

0x04 

 Only activate the vent when the thermostat operating state is heating or cooling. 

 

Default is 0x04 

 

Size 1 byte 

 

Содержание Building 36 ADC-T3000

Страница 1: ...Building 36 Technologies Alarm com Smart Thermostat Z Wave Manual V1 3 June 26 2019...

Страница 2: ...4 Select NETWORK 5 Select ADD 6 Thermostat will display Network Add In Progress and the 5 digit DSK pin The pin can be used for S2 inclusion 7 The thermostat has been added successfully when the ther...

Страница 3: ...k with other Z Wave certified devices from other manufacturers and or other applications All non battery operated nodes within the network will act as repeaters regardless of vendor to increase reliab...

Страница 4: ...enabled products can be added into a Z Wave network by scanning the Z Wave QR Code present on the product with a controller providing SmartStart inclusion No further action is required and the SmartS...

Страница 5: ...nted Security Class Humidity Control Mode 2 Highest Granted Security Class Humidity Control Operating State 1 Highest Granted Security Class Manufacturer Specific 2 Highest Granted Security Class Noti...

Страница 6: ...system When 24VAC is connected and 24VAC is detected the state is set It is cleared when 24VAC is not detected AC Mains Disconnected Set when 24VAC C Wire is not detected AC Mains Connected Set when 2...

Страница 7: ...ue is 0xFFFF e g 0x2AFFFF00 the parameter is disabled 5 1 Parameters 5 1 1 0x01 HVAC Type normal heat pump 0x00 Normal DEFAULT 0x01 Heat Pump Size 1 byte 5 1 2 0x02 Number of Heat Stages Auxiliary Hea...

Страница 8: ...4 bytes 5 1 11 0x0B RESERVED 5 1 12 0x0C Fan Circulation Period 10 to 1440 minutes Default 60 minutes Size 2 byte 5 1 13 0x0D Fan Circulation Duty Cycle 0 to 100 Default 25 Size 1 byte 5 1 14 0x0E Fa...

Страница 9: ...nts Default 50 F Size 4 bytes 5 1 19 0x13 Thermostat Lock 0x00 Disabled Default 0x01 Full Lock 0x02 Partial Lock Size 1 byte 5 1 20 0x14 Compressor Delay 0 to 60 minutes Default 5 minutes Size 1 byte...

Страница 10: ...T o 0x1F Off Heat Cool Auto Emergency Heat o 0x17 Off Heat Cool Emergency Heat o 0x13 Off Heat Emergency Heat Size 1 byte 5 1 25 0x19 Configurable Terminals Setting W3 H DH Vent 0x00 None DEFAULT 0x01...

Страница 11: ...o 0x00 Remote temperature disabled o 0x01 Active and functioning properly o 0x02 Inactive timeout reached see parameter 0x27 o 0x03 Inactive temperature differential reached See parameter 0x28 o 0x04...

Страница 12: ...An Alarm com Company 12 5 1 35 0x23 Z Wave Echo Association Reports 0x00 Disabled DEFAULT 0x01 Enabled Size 1 byte 5 1 36 0x24 C Wire Power Thermistor Offset Default 2 0 F Size 4 byte 5 1 37 0x25 Run...

Страница 13: ...Humidity Control Operating State Report o Bit 14 HVAC Type o Bit 15 Number of Cool Pump Stages o Bit 16 Number of Heat Aux Stages o Bit 17 Relay Status o Bit 18 Power Source C Wire or Battery o Bit 19...

Страница 14: ...ize 4 bytes 5 1 41 0x29 Remote Temperature ACK Failure Limit 0 127 Default is 3 Size is 1 byte 5 1 42 0x2A Remote Temperature Display Enable 0x00 Disabled 0x01 Enabled DEFAULT Size 1 byte 5 1 43 0x2B...

Страница 15: ...iguration Z1 Configuration Reserved Override Reserved HVAC Type 00b Normal 01b Heat Pump Fuel 0b Fuel 1b Electric Aux Fan 0b Disabled 1b Enabled Override 1b Relays manually configured 0b Relays automa...

Страница 16: ...FFFF Size 4 bytes 5 1 56 0x38 Vent Minimum Outdoor Temperature 0 F 99 F 1 F increments Default Disabled 0xFFFF Size 4 bytes 5 1 57 0x39 Relay Harvest Level Set PTO Harvest Level for Relay MCU energy h...

Страница 17: ...e humidity must change between reported humidity values 0 100 Default is 5 Size 1 byte 5 1 62 0x3E Z Wave Send Fail Limit If thermostat experiences successive Z Wave Transmit ACK failures exceeding th...

Страница 18: ...es if the vent configuration is not disabled and at least one configurable terminal is configured as vent Default is 12 hours Size is 1 byte 5 1 65 0x41 Humidify Options Humidify options 0x00 Always h...

Страница 19: ...sed on automatic wire detection Thermostat Fan State Report When fan state changes Humidity Control Operating State When humidity control state changes a humidity control operating state report is sen...

Страница 20: ...oint by 3 degrees Fahrenheit If the setpoint change causes the setpoints to be within 3 degrees Fahrenheit of eachother the setting is ignored For example if the heat setpoint was 72F and the cool set...

Отзывы: