• Fill the system with water in minimum pressure and vent the air. For minimum
pressure values see Table 5.3.
• Check the voltage values of the mains and compare with Table 5.2.
• Switch on the power to the pump.
• At first start-up the display is shown below:
• After one second:
• After one second minimum speed at manual mode is set for commissioning.
• Press “POWER” button to start the pump. To change the operating mode or
speed / head, see Section 7.
• The display goes into the sleep mode after 15 minutes if the buttons are
not pressed. Meanwhile, the pump continues to operate. The main menu is
shown by pressing any button.
• In case of a power outage, the pump saves its last operating mode settings
and resumes operating with those settings.
• To stop the pump, press “POWER” button.
Содержание OPTIMA
Страница 1: ...OPTIMA CIRCULATION PUMP INSTALLATION AND OPERATING INSTRUCTIONS ...
Страница 2: ...Kod No A 7 1 7i Publishment Date 280317 Revision Date 280317 Bulletin No 17 1004 ...
Страница 3: ...CIRCULATION PUMP INSTALLATION AND OPERATING INSTRUCTIONS ...
Страница 4: ...4 ...
Страница 34: ...34 The fault flowchart of the pump is given below Figure 11 1 Fault Flowchart ...
Страница 37: ...37 14 APPENDIX Dimension Table ...
Страница 38: ...38 Pump Selection Curves ...
Страница 40: ...40 4 12 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 41: ...41 5 8 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 42: ...42 5 9 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 43: ...43 5 12 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 44: ...44 6 12 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 45: ...45 8 12 Variable Pressure Operating Mode Constant Pressure Operating Mode Manual Operating Mode ...
Страница 46: ...46 ...
Страница 47: ...47 ...