Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
6
Signal type
Measurement range, °C
Temperature
coefficient, °C
-1
Accuracy, %
T
–200…+400
-
B
+200…+1800
TC according to GOST 8.585
L
-200…+800
-
±0.5
A-2
0…+1800
-
A-3
0…+1800
-
Table 2.4 Optional outputs
Ordering
code
Output type
Loading capacity
R
Relay
1 A (PID control) / 8 A (alarm)
30 V DC / 230 V AC, cos φ ≥ 0.4
T
NPN transistor
200 mA, 40 V DC
C
TRIAC
50 mA, 240 V AC (constant operation)
0.5 A (f
≤
50 Hz, pulse duration
≤
5 ms)
S
Solid state relay
100 mA, 4…6 V DC
I
4-20 mA
10…36 V, max. 1 kohm
U
0-10 V
15…36 V, min. 2 kohm
2.1
Environmental conditions
The device is designed for natural convection cooling that should be taken into account
when choosing the installation site.
The following environment conditions must be met:
–
clean, dry and controlled environment, low dust level
–
closed non-hazardous areas, free of corrosive or flammable gases
Table 2.5
Conditions
Permissible range
Ambient temperature
+1…+50°C
Storage temperature
-25…+55°C
Relative humidity
up to 80% (at +35°C, non-condensing)
Altitude
up to 2000 m above sea level