Operation and Configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
13
6
Operation and Configuration
6.1
Control elements
The device is designed in a plastic enclosure for panel or wall mounting, depending on
the model. The indicators and control elements are located on the front side of the device.
Fig. 6.1 Front view (H2 housing)
The operation of the device can be controlled with two 4-digit displays, three buttons and
eight LEDs on the front panel. The indicators inform the operator about the controller and
output status. Displays show following information:
Table 6.1 Displays
Display
Mode
Displayed information
Upper display
(red)
Operation
Process value
Configuration
Parameter name
Menu
“MENU”
Error
Error name
Lower display
(green)
Operation
Setpoint
Configuration
Parameter value
Menu
Parameter group
For display functions during the configuring see section 6.3 “Configuration”.
Table 6.2 Indicators
LED
Indication
Description
OUT1
lights
Output 1 is ON
OUT2
lights
Output 2 is ON
ALR
blinks
Alarm is activated
LBA
blinks
Loop Break Alarm is activated
STOP
lights
Control is stopped by user
blinks
Control is stopped due to a hardware error or LBA
AT
lights
Autotuning in progress
blinks
Autotuning failure
COM
flashes for 0.1 s
on data transmission
MAN
lights
Manual control is activated
OUT1 OUT2 COM
ALR LBA MAN
STOP
AT
TRM210