Appendix B Configuration parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
33
No
Name
Display
Parameter
Valid value
Meaning
Factory
3
dP
dP
Decimal point
(2)
0
0000
1
1
000.0
2
00.00
3
0.000
4
in-L
in- L
Signal lower limit
(2)
–1999...9999
affected by
dP
0.0
5
in-H
in- H
Signal upper limit
(2)
–1999...9999
affected by
dP
100.0
6
SL-L
SL- L
Setpoint lower limit
-1999...9999
affected by
dP
-199.9
7
SL-H
SL- H
Setpoint upper limit
-1999...9999
affected by
dP
800
8
SH
SH
Offset
-500…500
affected by
dP
0.0
9
KU
KU
Slope
0.5…2.0
-
1.000
10
Fb
Fb
Filter bandwidth
0….9999
affected by
dP
0.0
11
inF
INF
Filter time constant
OFF
-
OFF
1…999 s
12
ALt
ALT
Alarm mode
00
OFF
00
01
outside range
SP ± AL-d
02
greater than
SP ± AL-d
03
less than
SP ± AL-d
04
within range
SP ± AL-d
05
01 with blocking
of the first alarm
06
02 with blocking
of the first alarm
07
03 with blocking
of the first alarm
08
greater than AL-d
09
less than
AL-d
10
08 with blocking
of the first alarm
11
09 with blocking
of the first alarm
13
AL-d
AL- d
Alarm threshold
in-L
…
in.H
not displayed
when
ALt
= 00
10.0
14
AL-H
AL- H
Alarm hysteresis
in-L
…
in.H
not displayed
when
ALt
= 00
0.0
15
An-L
An- L
Retransmission lower limit
(3)
-1999...9999
affected by
dP
0.0
16
An-H
AN- H
Retransmission upper
limit
(3)
-1999...9999
affected by
dP
100.0
17
Ev-1
Eu- 1
DI function
nonE
OFF
nonE
n-o
Start with open
contact
n-C
Start with closed
contact
18
orEU
OrEU
Control function
or-d
Cooling
or-d
or-r
Heating
19
CP
CP
Pulse period
1…250 s
1