351652602 Ed. 03
35
Inputs and outputs
Level 1
Level 2
Description
Values Min. Def. Max.
InO
I60
Pressure units: 0=bar, 1=Psi
0
*
1
I61
Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V,
4=0-10 V, 5=1-5 V
0
0
5
I62
Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V)
-1
0
I63
I63
Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V)
I62 12
60
I64
Pressure sensor calibration (S2)
-10
0
10
o00
AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance,
2=light, 3=virtual control, 4= alarm, 5=resistor door frame
0
*
5
o10
AUX 2 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=virtual control,
4=defrost 2
nd
evaporator, 5=resistor. door frame, 6=equal solenoid status,
7=equal device status
0
2
7
o20
AUX 3 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=external AO
controller ON/OFF, 4=defrost 2
nd
evaporator, 5=resistor. door frame
0
0
5
o30
Analogue output type (AO): 0=4-20 mA, 1=0-10 V
0
0
1
EP
Output to level 1
HACCP alarm
Level 1
Level 2
Description
Values Min. Def. Max.
HCP
h1
HACCP alarm maximum temperature
ºC/ºF -50 99.0 99.0
h2
Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm
deactivated)
h.
0
0
255
EP
Output to level 1
Information (read-only)
Level 1
Level 2
Description
Values Min. Def. Max.
tid
InI
Option chosen in the configuration wizard
Pd
Pump down active? 0=no, 1=yes
PU
Software version (Information)
Pr
Program revision
PSr
Program Subversion
bU
Bootloader version
br
Bootloader revision
bSr
Program Subversion
PAr
Parameter map revision
EP
Output to level 1
* According to the set-up wizard.