351652602 Ed. 03
18
Continuous cycle mode
This is used to quickly cool the cold room stores before
products are loaded and is activated by pressing the
key for 3 seconds.
Upon activating this mode, the compressor begins to
operate until the temperature in sensor S1 reaches the
set point value, minus the variation indicated in param-
eter C10. The value of C10 is always negative, unless
it is 0.
The unit will immediately return to normal operation.
Should it not be possible to reach this point, the de-
vice will return to normal operation once the time con-
figured in C9 has elapsed, or by pressing the
key
again for 5 seconds.
Set Point change mode
This allows for quick alternation between two working temperatures in the cold room store, modifying the Set Point
in line with the value indicated in parameter C12. The aforementioned value may be negative or positive, which
allows for the Set Point to be reduced or increased. If it is configured in 0, the mode is disabled.
It is activated in three possible ways:
By means of an external switch connected to one of the digital inputs. The digital input should be configured as
“Set Point change” (I10 or I20=4). Activation through this method cancels any other activation and can only be
deactivated using the same method.
By means of the AKONet application. This requires the device to be connected to a Modbus network (See page 36).
By means of the CAMM module and the AKO CAMM tool application.
EXAMPLE:
Calibration of sensor 1
Parameter C0 allows for correction of the temperature detected by sensor 1; this is particularly useful when the
sensor cannot be located in the ideal place.
Set Point locking
Parameters C2 and C3 allow for an upper and lower limit to be established for the set point (SP), to protect the
product or installation from Set Point manipulation.
Solenoid
Solenoid
Configuration
Set Point
change
Solenoid
Solenoid
Configuration
Set Point
change