1.- Presentation
PROPlus 3PH is the global electronic solution to manage positive and negative cold room stores, in combination
with:
Ÿ
Standard condensing units
Ÿ
Streamlined condensing units
Ÿ
Or as a service panel in decentralised systems.
It offers a high degree of IP65 protection for installation in damp environments. It is easy to install thanks to its
new connection strip.
1.1.- Maintenance
Clean the surface of the unit with a soft cloth, water and detergent. Do not use abrasive detergents, petrol, white
spirits or solvents.
1.2.- Precautions
Using the equipment without following the manufacturer's instructions may affect the device's safety requirements.
To ensure that the device operates correctly, only probes supplied by AKO should be used.
Between -40 ºC and +20 ºC, if the NTC probe is extended up to 1,000 m with minimum 0.5 mm² wire, the
maximum deviation will be 0.25 ºC (Wire for probe extension ref.
AKO-15586
)
IMPORTANT:
Ÿ
The AUX 1, AUX 2 and AUX 3 relays are programmable, and their operation depends on the
configuration (see page 25).
Ÿ
The function of the digital inputs depends on the configuration (See page 26).
Ÿ
The recommended currents and powers are the maximum working currents and powers.
2.- Versions and references
Condensing
unit
Condenser
fans
Evapor
ator
fan
Defr
ost
resistances
Light
Power supply
AKO-15690
2,5 - 4 A
3 A
(I+N)
4 A
(I+N)
7.000 W
1 A
(230 W)
400 V / III
50/60 Hz
AKO-15691
4 - 6,3 A
AKO-15692
6,3 - 10 A
10.200 W
AKO-15693
10 - 16 A
AKO-15697
-
-
5 A (I+N)
AKO-15699
1.6 - 2.5 A (III+N)
AKO-15699-1
-
-
6.3 - 10 A (I+N)
20.000 W
AKO-15690-EVC
2,5 - 4 A
3 A
(I+N)
4 A
(I+N)
7.000 W
AKO-15691-EVC
4 - 6,3 A
AKO-15692-EVC
6,3 - 10 A
10.200 W
AKO-15693-EVC
10 - 16 A
AKO-15697-EVC
-
-
5 A (I+N)
AKO-15699-EVC
1.6 - 2.5 A (III+N)
3
1569H042 Ed.03