6.2- Messages
9
* Requires auxiliary alarm 2 to be configured as alarm relay (P62=1)
Flashing 0: Access code (Password) request
You must enter the access code configured on L5 to execute the requested
function (p. 19).
See also parameter P2 (p. 25)
Probe 1 or 2 faulty
(open circuit, crossover or temperature outside the probe limits;
NTC
: -50
To 99 ºC).
(Activates alarm relay and sound alarm) *
Indicates a defrost is underway. When the defrost process has finished, the
message will continue to be displayed during the time defined in parameter
d3 (see Chapter 9.2).
Alternating with temperature:
Maximum temperature in control probe alarm. Temperature set in A1 has
been reached (p. 18)
(Activates alarm relay and sound alarm) *
Alternating with temperature:
Minimum temperature in control probe alarm. Temperature set in A2 has
been reached (p. 18).
(Activates alarm relay and sound alarm) *
Alternating with temperature:
External alarm activated (by digital input) (p. 18).
(Activates alarm relay and sound alarm) *
Alternating with temperature:
Severe external alarm activated (by digital input) (p. 18).
(Activates alarm relay and sound alarm) *
Alternating with temperature:
Defrost alarm time-out. Displayed when a defrost ends after the maximum
time elapsed as defined in parameter d1. (p. 18).
(Message only displayed on screen)
Alternating with temperature:
Door open alarm. Shown if the door remains open longer than specified in
parameter A12 (p. 18).
(Activates alarm relay and sound alarm) *
Alternating with temperature:
The maximum pump down stop time has been exceeded (
P15
)
(p. 18) (Message only displayed on screen)
Alternating with temperature:
The maximum pump down start-up time has been exceeded (
P14
) (p. 19)
(Message only displayed on screen)
It indicates that a component in the compressor's safety chain has triggered
(compressor motor guard, thermistors or high pressure controller). (Pág. 19)