1569H042 Ed.03

18

9.6.- Alarms

The unit warns the user with a message on the screen of the activation of a relay or the activation of an acoustic signal in 
certain circumstances, according to the programming of the following parameters.

Max/Min Temperature Alarm

Shows the 

AH 

or 

AL 

message when the temperature in probe 1 reaches the value set in 

the 

A1

 (maximum temperature) or 

A2

 (low temperature) parameters.

This value can be:

Absolute (A0=1): A1/A2

 should indicate the temperature at which the alarm should 

be activated.

Relative  to  SP  (A0=0):  A1/A2

  should  indicate  the  number  of  degrees  above  or 

below  the  set  point  at  which  the  alarm  is  activated.  This 
option allows users to adjust the set point without having to 
modify the high and low alarm settings.

Parameter 

A10

 sets the differentials for both parameters (hysteresis).

Activates alarm relay (if 

P62=

1) and sound alarm.

Example

In a controller we configure the following parameters: 

SP

=2, 

A1

=10, 

A10

=2

- If A0=0 (relative to SP), the maximum temperature alarm goes off when probe 1 reaches 12 degrees 

and is disabled when it reaches 10 degrees. 

- If A0=1 (absolute), the maximum temperature alarm goes off when probe 1 reaches 10 degrees and is 

disabled when it reaches 8 degrees.

External alarm/severe external alarm

Displays  the  message 

AE 

(external  alarm)  or 

AES 

(severe  external  alarm),  when  the  digital 

input configured as external alarm or severe external alarm is activated.
The severe external alarm also deactivates all the charges, therefore, the temperature regulation 
is stopped. When this alarm disappears the device returns to its normal operation.
At least one of the digital inputs must be configured as external alarm (

P10 

or

 P11

=2) or severe external alarm 

(

P10 

or

 P11

=3).

Activates alarm relay (if 

P62=

1) and sound alarm.

Defrost alarm completed by time.

Shows the 

Adt 

alarm message when a defrost terminates by time-out, if parameter 

A8

=1.

DOES NOT

 activate the alarm relay or the sound alarm, it is only shown on the display.

Door open alarm 

Displays the 

PAb

 message when the door stays open for a time greater than that set with parameter 

A12

. (One of 

the digital inputs must be configured as door contact (

P10 or P11=

1).

Activates alarm relay (if 

P62=

1) and sound alarm.

Pump down malfunction error (Stop)

Displays  the 

Pd

  message  if  a  malfunction  is  detected  when  the  installation  is  stopped 

using the pump down manoeuvre. (See page 17).

DOES NOT

 activate the alarm relay or the sound alarm, it is only shown on the display.

Содержание AKO-15690

Страница 1: ...AKO 1569x AKO 1569x EVC PROPlus 3PH BASIC Electronic Panel GB 1569H042 Ed 03 User Manual...

Страница 2: ...these regulations Rigorouslyfollowtheinstructionsdescribedinthismanual Inordertoextendthelifetimeofourproductstothemaximum thefollowingpointsmustbeobserved Do not expose electronic equipment to dust...

Страница 3: ...C and 20 C if the NTC probe is extended up to 1 000 m with minimum 0 5 mm wire the maximum deviation will be 0 25 C Wire for probe extension ref AKO 15586 IMPORTANT The AUX 1 AUX 2 and AUX 3 relays ar...

Страница 4: ...emovecover B Using the included template make 4 holes in the wall and fasten the unit to the wall using the supplied screws Makeaholeinthebottomoftheboxtopassthecablesthrough andasuitableglandshouldbe...

Страница 5: ...tor guard Q1 according to the obtained value The setvalueshouldneverbehigherthantheconsumptionindicatedbythemanufacturer 11 5 A A 1 2 I O 1 0 16 10 1 6 Q1 AKO 15690 1 2 3 AKO 15690 1 2 3 EVC AKO 15699...

Страница 6: ...1569H042 Ed 03 A B C C C 6 D Remove the front trims A and screw the cover on using the included screws B Theninstallthetrimsagain ALL MODELS...

Страница 7: ...he panel up Powersupplyvoltagesandfrequencieswillbetheonesthatfigureinthe Technicalspecifications section Checkthattherearenoloosepartsorforeignbodiesonconnectionsorswitchgear Checkthatthereisnodustor...

Страница 8: ...ing it for 5 seconds allows changing the SETPOINTtemperature Pressing it for 5 seconds activates or deacti vatestheCONTINUOUSCYCLE Pressing it for 5 seconds the quick setup menu is accessed Pressing i...

Страница 9: ...ctivates alarm relay and sound alarm Alternating with temperature External alarm activated by digital input p 18 Activates alarm relay and sound alarm Alternating with temperature Severe external alar...

Страница 10: ...frost circuit breaker FM Operation circuit breaker Q1 Compressor motor guard Q3 Evaporator fan motor guard K1M Compressor contactor K2M Defrost contactor K4M Evaporator fan contactor T2 EVC Transforme...

Страница 11: ...ne high low pressure controller AKO 15690 1 2 3 AKO 15690 1 2 3 EVC Separate Low pressure controller per AC input AKO 15690 1 2 3 AKO 15690 1 2 3 EVC Pressure controller equivalence HIGH LOW 16 16 17...

Страница 12: ...requency Time that must elapse between the starting of each defrost see page 15 d1 Maximum defrost duration The defrost will end after this time has elapsed since it started F3 Fan status during defro...

Страница 13: ...he temperature in probe 1 reaches the set point value SP plus the probe s differential C1 the compressor activates and makes the temperature drop When the set point value SP is reached thecompressorst...

Страница 14: ...ill operate according to the average performance of the last 24 hours taking into account the number of starts and stops and the average time in each state stop start C6 3 The compressor will run as s...

Страница 15: ...termination The defrost will terminate if The temperature programmed in parameter d4 has been reached in probe 2 Probe 2 must be activated P4 In the event of probe 2 failure defrosting will be complet...

Страница 16: ...account parameters F2 to F5 Parameter F2 defines the status of the fans during compressor stops Parameter F3 defines the status of fans during defrost Parameter F4 defines the fan start up delay afte...

Страница 17: ...or the sound alarm it is only shown on the display STARTUP When temperature probe 1 reaches the set point value plus the differential SP C1 the AUX 1 relay is activated ON opening the liquid solenoid...

Страница 18: ...n probe 1 reaches 10 degrees and is disabled when it reaches 8 degrees External alarm severe external alarm Displays the message AE external alarm or AES severe external alarm when the digital input c...

Страница 19: ...rature alarm A5 Delays activation of maximum A1 and minimum A2 temperature alarms from the moment temperature probe 1 reaches the set value Delay of external alarm activation A6 Delays the activation...

Страница 20: ...ly Connect the programming key in the parameter server connector Connect the power supply for the programming key Press the READ key on the programming key Disconnect the device programming key Transf...

Страница 21: ...PC Up to 127 units can be connected to a PC with AKONet AKO 5010 or to the AKO 5011 web server Each of these unitsshouldhaveadifferentMODBUSaddress thatisdefinedusingtheP5 Using the AKONet software it...

Страница 22: ...Thisfunctionconfiguresalltheunit sparameterstoitsdefaultvalues i e asitleavesthefactory In order to return the computer to its initial settings go to the programming menu and set parameter P3 to 1 The...

Страница 23: ...Protectiondelaytime valueoftheoptionselectedinparameterC4 Page14 min 0 0 120 C6 StatusofCOMP relaywithprobefault Page14 0 OFF 1 ON 2 Averagebasedonlast24hourspriortoprobefault 3 ON OFFasprog C7andC8...

Страница 24: ...1 YES Firstdefrostasperd6 0 0 1 d6 Defroststartdelayonequipmentstart up Page16 min 0 0 255 d8 Calculatedtimebetweendefrostperiod Page16 0 Totalactualtime 1 Sumoftimesthecompressorison 0 0 1 d9 Driptim...

Страница 25: ...Alarmrelaypolarity 0 RelayONinalarm OFFnoalarm Page19 1 RelayOFFonalarm ONwithnoalarm 0 0 1 A10 TemperatureAlarmDifferential A1andA2 Page18 C F 0 1 1 0 20 0 A12 Dooropenalarmdelay ifP10orP11 1 Page19...

Страница 26: ...sec 0 0 120 P15 Maximumpumpdowntime Page17 0 Disabled min 0 0 15 P22 Coldroomlighttimer Page16 min 0 0 999 P23 Stopfansandcompressoronopeningdoor Page14 0 No 1 Si 0 0 1 P24 Startupdelayforfansandcompr...

Страница 27: ...cisionoftheNTCprobeat25 C 0 4 C InputforNTCprobe AKO 14901 Maximuminputpowerintheoperation 30VA Workingambienttemperature 5 Cto40 C Storageambienttemperature 30 Cto70 C Overvoltagecategory IIs EN61439...

Страница 28: ...ials that might vary slightly to those described in our Technical Sheets Updated information is available on our website AKO ELECTROMEC NICA S A L Avda Roquetes 30 38 08812 Sant Pere de Ribes Barcelon...

Отзывы: