3516526A02 Ed. 01
40
Inputs and outputs
Level 1
Level 2
Description
Values Min. Def. Max.
In0
o00
AUX1 relay configuration: 0= Deactivated, 1= Compressor/Crankcase resist-
ance, 2= Light, 3= Virtual control, 4= Alarm, 5= Door frame resistor,
6=Drainage resistor
0
*
6
o10
AUX2 relay configuration: 0= Deactivated, 1= Alarm, 2= Light, 3= Virtual
control, 4= Defrost 2nd evaporator, 5= Door frame resistor, 6= Equal solenoid
status, 7= Equal device status, 8=Drainage resistor
0
2
8
o20
AUX3 relay configuration: 0= Deactivated, 1= Alarms, 2= Light,
3= External AO controller ON/OFF, 4=Defrost 2nd evaporator,
5= Door frame resistor, 6=Drainage resistor
0
0
6
o30
Analogue output type (AO): 0= 4-20mA, 1= 0-10V
0
0
1
EP
Output to level 1
HACCP alarm
Level 1
Level 2
Description
Values Min. Def. Max.
HCP
h1
HACCP alarm maximum temperature
ºC/ºF -50 99.0 99.0
h2
Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm
deactivated)
h.
0
0
255
EP
Output to level 1
Information (read-only)
Level 1
Level 2
Description
Values Min. Def. Max.
tid
InI
Option chosen in the configuration wizard
Pd
Pump down active? 0=No, 1=Yes
PU
Program version
Pr
Program revision
PSr
Program subrevision
bU
Bootloader version
br
Bootloader revision
bSr
Bootloader subrevision
PAr
Parameter map revision
EP
Output to level 1
* According to the set-up wizard.