3516526A02 Ed. 01
35
Parameters
Regulation and control
Level 1
Level 2
Description
Values Min. Def. Max.
rE
SP
Temperature setting (Set Point)
ºC/ºF -50 0.0 99
CE
SELFDRIVE Mode 0=Deactivated 1= Activated
0
1
1
C0
Sensor 1 calibration (Offset)
ºC/ºF -4.0 0.0 4.0
C1
Sensor 1 differential (Hysteresis)
ºC/ºF 1.0 2.0 20.0
C2
Set point top locking
(it cannot be set above this value)
ºC/ºF
C3 99
99
C3
Set point bottom locking
(it cannot be set under this value)
ºC/ºF -50 -50 C2
C4
Type of delay for the protection of the compressor:
0=Minimum OFF time of the compressor
1=Minimum OFF and ON time of the compressor in each cycle
0
0
1
C5
Protection delay time
(Value of the option selected in parameter C4)
min.
0
0
120
C6
COOL relay status with fault in sensor 1:
0=OFF; 1=ON; 2=Average according to last 24 h before the sensor error;
3=ON-OFF according prog. C7 and C8
0
2
3
C7
Time of relay ON if sensor 1 damaged
(If C7=0 and C8
¹
0, the relay will always be OFF when disconnected)
min.
0
10 120
C8
Time of relay OFF if sensor 1 damaged
(If C8=0 and C7
¹
0, the relay will always be ON when connected)
min.
0
5
120
C9
Maximum duration of the continuous cycle mode. (0=deactivated)
h.
0
0
48
C10
Variation of the Set Point (SP) in continuous cycle mode. When it reaches this
point (SP+C10), it reverts to the normal mode. (SP+C10
³
C3).
The value of this parameter is always negative, unless it is 0. (0=OFF)
ºC/ºF
0
-50
C3-
SP
C12
Variation of the set point (SP) when the change set point change function is
active. (SP+C12
£
C2) (0= deactivated)
ºC/ºF
C3-
SP
0
C2-
SP
C19
Maximum time for start-up after gas collection
(Values between 1 and 9 seconds are not accepted) (0= Deactivated)
sec.
0
0
120
C20
Maximum time for pump down (0= deactivated)
min.
0
0
15
C22
Stop fans and COOL when opening door 0=No 1=Yes
0
0
1
C23
Start-up delay for fans and COOL when door open
min.
0
0
999
C24
Delay time of cold stop with door open.
sec.
0
0 C23
C25
Influence of probe S3 when regulating with two temperature probes (I20=10)
(See page 20)
%
0
0
95
C27
Sensor 4 calibration (Offset)
ºC/ºF -4.0 0.0 4.0
EP
Output to level 1
**In Selfdrive mode
Содержание 16526A
Страница 43: ...3516526A02 Ed 01 43...