Web Server
~
24
~
a
The sum of the rated power of all inverters in the PV plant
(Wac)
b
The percentage of power output limitation based on
parameter b
Parameter a: This parameter is the key value of power limitation, please ensure that
it is correct
◼
Power Limitation Based on the Energy Meter Reading
In this method the export power of the PV system at the point of connection will not
exceed the value that is set in the energy meter. For example, if a 1 kWac export limit
has been set in the energy meter then a 2 kWp PV system connected to an Eversol
TL2000 (2 kWac inverter) will reduce its AC output to ensure that the export power
at the point of connection will not exceed 1 kWac.
Fig. 6-8 shows the system diagram of power limitation based the energy meter reading.
Currently, only the Eastron SDM630DC energy meter is supported.
c
Fig. 6-7 System diagram based on the energy meter reading
For this method position 3 in Fig. 6-9 should be ticked.
Click the “OK” button in bottom
-right of this web page to ensure the setting