11
ICE EX04-18 Heat I&O Manual 06/2020 Rev.1
The factory default operation password of the unit is “0001”. To change it, press
ENTER
on the normal display interface to enter the password input interface, press the
LEFT
button or
RIGHT
button to select the digits to change, and press the
UP/DOWN
button
to change the relevant digits, and finally press
ENTER
button to confirm the change.
If the password is incorrect, the interface will display an error message, and the unit
setting cannot be changed. If the password is correct, you can enter the main menu and
edit the unit setting.
Note:
The above diagram is unit menu structure, not the factory setting.
Chapter 4: Maintenance
WARNING
All maintenance shall be performed by qualified persons. Always disconnect the
power, communication and alarm output cables from the heat exchanger before
any maintenance and do not reconnect them until the maintenance is completed.
To maintain full performance of a heat exchanger operating in a harsh environment,
preventative maintenance should performed every six months.
Note:
Make sure all the power input is shutoff before any maintenance work is done.
Tool lists:
1. Air compressor or a dedicated clean water gun
2. Brush
3. Cleaning towels
4. Screw driver
4.1 Filter
This heat exchanger has no filters; the cabinet provides air filtration. Any debris
blocking the openings will reduce air into the heat exchanger, thereby reducing its
performance.