5-5
PERFORMANCE DATA
SM DUO38I 1-A.2 GB
5.3 WDI
9-12
5.3.1
Cooling Capacity (kW) - Run Mode(Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [
O
C]
OD COIL
ENTERING AIR DB
TEMPERATURE [
O
C]
DATA 22/15 24/17 27/19 29/21 32/23
-10 - 20 (protection
range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC 3.27 3.46 3.65 3.84 4.04
SC 2.22 2.27 2.33 2.38 2.43
PI 0.67 0.68 0.70 0.71 0.72
30
TC 2.97 3.16 3.35 3.54 3.73
SC 2.11 2.16 2.21 2.27 2.32
PI 0.75 0.76 0.77
0.79 0.80
35
TC 2.67 2.86
3.05
3.24 3.43
SC 1.99 2.05
2.10
2.15 2.21
PI 0.82 0.84
0.85
0.86 0.88
40
TC
80%-92% of nominal
SC
80%-92% of nominal
PI
80%-100% of nominal
46
TC
70%-85% of nominal
SC
70%-85% of nominal
PI
90%-100% of nominal
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
5.3.2
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20
25
30
35
40
45
Outdoor Temperature [deg C]
Ca
pa
ci
ty
Ra
ti
on