2 - INSTALLATION
Avoid installations next to bedrooms or windows.
Consider sound emissions
2.2- MAXIMUM DISTANCE
Refrigerant pipes:
in vertical sections ensure the presence of siphons every six
metres of unevenness (on the supply/suction line only).
A
max 25 m
equivalent length of the pipe lines
B
max 15 m
height difference
C
6 m
6 m back up → siphon (gas line)
2.3 - OUTDOOR UNIT
Keep the min. distances from the podestrian areas.
Consider clearances and direction of expelled air.
Provide windbreaks (or similar) in locations with strong winds.
A
Provide a protection.
B
Avoid snow accumulations on batteries.
C
Install the unit lifted from the ground.