47
Password-protected unit parameters (only for the installer)
Tab.1
PAC BT is set by the factory with default unit parameters to values that can satisfy the greater number of installation cases.
For a detailed customization of the system is however possible to make changes; the following is a list of all unit parameters, with all
the available settings.
According to the unit configuration some parameters are visible and some not.
7 - CONTROL
Num.
descrizione
descrizione estesa
3
EnCCar
Enable charge compensation
0=No
1=Cool
2=Heat
3=Always
6
CompDutyEn
Enable compensation on duty
0=No
1=Cool
2=Heat
3=Always
7
DemandLimtEn
Enable Demand Limit
0=None
1=auxiliary release priority
2=compressor release priority
3 = Current measurement
8
CompOnEn
Enable compensation on the duration
0=None
1=cooling only
2= heating only
3=Always
12
EnH2OSan
Enable DHW managing
0=No DHW,
1=DHW and inst. mode without restrictions,
2=DHW and heat only installation,
3=DHW and cool only installation,
4=DHW only mode
13
CaldaiaEN
Enable boiler fu Heat pump
0= disabled,
1= enabled
18
EnPAux
Enabling auxiliary heater
0= Disabled,
1= Enabled,
2= Enabled (does not intervene for compressor failure in DHW)
19
ControlMode
Enables the automatic control of temperatures
24
ControlPump
Enables the utility pump switching off:
0=Not enabled (always on)
1 = in function of the environment call (from electromechanical thermostat or remote)
2= in function of the installation tank temperature( not accepted configuration by PAC BT)
26
EnPowerLimit
Enable Power Limit
33
EnControlHC
Enable automatic variation of mode change
188
LimI
Current limit
199
TimePTS
Cycle time for discharge temperature limitation
314
CanAddress
Board CAN address
1=Hydronic board (Master – Indoor )
2= Refrigeration board (Slave – Outdoor
315
Address
ModBus supervision serial address
316
BaudRate
Baud Rate supervision serial
0=4800
1=9600
2=19200
317
Parity
Parity supervision serial
0=NO
1=Odd
2=Even
321
TimeOutRete
Modbus network timeout
ATTENTION
The access to parameters or modifications are allowed only to the installer who assumes all responsibility, in case of doubts please
contact Airwell.
For any changes not permitted or not approved by Airwell, the same declines any responsibility for malfunctions and/or damages to
the unit/system.
Содержание PAC BT Series
Страница 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Страница 2: ......
Страница 4: ......
Страница 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Страница 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Страница 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Страница 99: ...Airwell Residential 42 68 8 8 10 XL kW kW kW AWAU PAC BT UE 12KW H13 AWHK PAC BT UI 12 17KW H11...
Страница 103: ...Airwell Residential 42 69 9 10 12 XL kW kW kW AWAU PAC BT UE 14KW H13 AWHK PAC BT UI 12 17KW H11...
Страница 107: ...Airwell Residential 42 70 11 11 14 XL kW kW kW AWAU PAC BT UE 17KW H13 AWHK PAC BT UI 12 17KW H11...
Страница 111: ......