Indoor unit cassette type
ENGLISH
3. INSTALLATION/SERVICE TOOLS (Only for R410A product)
Gauge manifold
New tools for
R410A
New tools for R410A
Applicable to R22 model
Changes
Charge hose
Electronic balance
for refrigerant
charging
Torque wrench
(nominal dia. 1/2,
5/8)
Flare tool
(clutch type)
Gauge for
projection
adjustment
As the working pressure is high, it is impossible to
measure the working pressure using conventional
gauges. In order to prevent any other refrigerant from
being charged, the port diameters have been changed.
In order to increase pressure resisting strength, hose
materials and port sizes have been changed (to 1/2
UNF 20 threads per inch). When purchasing a charge
hose, be sure to confirm the port size.
As working pressure is high and gasification speed is
fast, it is difficult to read the indicated value by means
of charging cylinder, as air bubbles occur.
The size of opposing flare nuts have been increased.
Incidentally, a common wrench is used for nominal
diameters 1/4 and 3/8.
By increasing the clamp bar's receiving hole size,
strength of spring in the tool has been improved.
Ne
w Refrigerant Air
Conditione
r Installation
THIS
AIR
CONDITIONE
R
ADOPTS TH
E
NE
W
HFC REFRIGERANT
(R410A)
WHICH DOES
NOT DESTRO
Y
OZON
E
L
AYER.
R410A refrigerant is apt to be affected by impurities such as
water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx.
1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the
refrigeration machine oil has also been changed. Therefore, during installation work, be sure that
water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type
refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of
charging port on main unit and installation tools are different from those used for the conventional
refrigerant units. Accordingly, special tools are required for the new refrigerant (R410A) units. For
connecting pipes, use new and clean piping materials with high pressure fittings made for R410A
only, so that water and/or dust does not enter. Moreover, do not use the existing piping because
there are some problems with pressure fittings and possible impurities in existing piping.
Change
s in the product and components
In air conditioners using R410A, in order to prevent any other refrigerant from being accidentally
charged, the service port diameter size of the outdoor unit control valve (3 way valve) has been
changed. (1/2 UNF 20 threads per inch)
In order to increase the pressure resisting strength of the refrigerant piping, flare processing
diameter and opposing flare nuts sizes have been changed. (for copper pipes with nominal
dimensions 1/2 and 5/8)
CAUTION
Used when flare is made by using conventional flare
tool.
4
Содержание KCD
Страница 2: ...10 REFRIGERANT TUBING 18 11 PANEL INSTALLING 20 22 FINAL TASKS 12 1 Indoor unit cassette type 14 16 ...
Страница 14: ...Indoor unit cassette type 13 80mm 80mm Ø75mm MODLE 24 48 Model 24 48 INVERTER 24 48 A 160mm B 95mm NOTE Fig 11 ...
Страница 24: ......
Страница 25: ...DEUTSCH Deutsch Montageanleitung CCD KCD DCC ...
Страница 48: ......
Страница 49: ...FRANCAIS Manuel d installation CLIMATISEUR CASSETTE Type de d unité intérieure cassette CCD KCD DCC ...
Страница 72: ......
Страница 73: ...ESPAÑOL ACONDICIONADOR DE AIRE TIPO CASSETTE Manual de Instalación Unidad Interior Tipo Cassette CCD KCD DCC ...
Страница 96: ......
Страница 120: ......
Страница 121: ...РУССКИЙ Руководство по установке БЛОК ДЛЯ КОНДИЦИОНИРОВАНИЯ ВОЗДУХА Блок внутреннего типа CCD KCD DCC РУССКИЙ ...
Страница 144: ......